Operating Instructions

Chapter 4 - Parameters and Menu Structure
I/O and Hardware (M5)
136 | 187
Siemens Industry, Inc.
Siemens BT300 HVAC Drive
DPD01809
Smart Infrastructure
2019-05-29
Instance ID
Object Name
Description
Active/Inactive Text
PV Access
Menu
BV_0
READY STATE
Status of the Ready State.
READY/NOTRDY
R
V2.2.17
BV_1
RUNENBL STAT
Status of Run Enable, regardless
of the control source.
ENABLE/DISABL
R
V2.2.17
BV_2
RUNSTP STAT
Status of Run Stop, regardless of
the control source.
RUN/STOP
R
V2.2.17
BV_3
FWD REV STAT
Status of Forward/ Reverse,
regardless of the control source.
REVRSE/FORWRD
R
BV_4
FAULT STATUS
Status of Fault, regardless of the
control source.
FAULT/NOFLT
R
BV_5
ALARM STATUS
Status of Alarm, regardless of the
control source.
ALARM/NORMAL
R
BV_6
AT ZERO
Motor is running at Zero speed.
TRUE/FALSE
R
BV_7
AT SETPOINT
Motor is running at Setpoint.
TRUE/FALSE
R
BV_8
RO1 STATUS
Status of relay output 1.
ON/OFF
R
P5.1.13
BV_9
RO2 STATUS
Status of relay output 2.
ON/OFF
R
P5.1.14
BV_10
RO3 STATUS
Status of relay output 3.
ON/OFF
R
P5.1.15
BV_11
M1 STATUS
Status of M1 contactor (if e-
bypass enabled).
CLOSED/OPEN
R
BV_12
M2 STATUS
Status of M2 contactor (if e-
bypass enabled).
CLOSED/OPEN
R
BV_13
FBDATAOUT1B0
Fieldbus Process Data Out 1 Bit
0
ON/OFF
R
BV_14
FBDATAOUT1B1
Fieldbus Process Data Out 1 Bit
1
ON/OFF
R
BV_15
FBDATAOUT1B2
Fieldbus Process Data Out 1 Bit
2
ON/OFF
R
BV_16
FBDATAOUT1B3
Fieldbus Process Data Out 1 Bit
3
ON/OFF
R
BV_17
FBDATAOUT1B4
Fieldbus Process Data Out 1 Bit
4
ON/OFF
R