Operating Instructions

Chapter 4 - Parameters and Menu Structure
I/O and Hardware (M5)
140 | 187
Siemens Industry, Inc.
Siemens BT300 HVAC Drive
DPD01809
Smart Infrastructure
2019-05-29
Point
Number
Point
Type
Subpoint Name
Factory
Default
Engr. Units
Slope
Intercept
On Text
Off Text
Drive Menu
1
LAO
CTRL ADDRESS
99
1
0
2
LAO
APPLICATION
2770
1
0
3
LDI
AT SETPOINT
OFF
ON
OFF
4
LAI
CURRENT
0
A
0.1
0
M2.2.4
5
LAI
DC BUS VOLT
0
V
0.1
0
M2.2.10
6
LDI
DRIVE READY
READY
READY
NOT READY
M2.2.17 Bit 1
7
LAI
DRIVE TEMP
0
ºF
0.18
-58
M2.2.11
8
LAI
FREQ OUTPUT
0
HZ
0.1
-320
M2.2.1
9
LAI
MOTOR TEMP
0
%
0.1
0
M2.2.12
10
LAI
PCT OUTPUT
0
%
0.01
0
M2.8.12
11
LAI
POWER
0
%
0.1
0
M2.2.7
12
LAI
SPEED
0
RPM
1
0
M2.2.3
13
LAI
TORQUE
0
%
0.1
0
M2.2.5
14
LAI
VOLTAGE
0
V
0.1
0
M2.2.9
15
LAI
FIREMODESTAT
0
1
0
P3.16.7
16
LAI
DRIVE KWH
0
KWH
0.1
0
P4.4.1
17
LAI
DRIVE MWH
0
MWH
0.1
0
P4.4.1
18
LAI
RUN TIME
0
HRS
10
0
P4.4.7
20
LAO
OVRD TIME
1
HRS
1
0
21
LDO
RUN ENABLE
STOP
ENABLE
STOP
P3.5.1.11
22
LDO
CMD FWD.REV
FWD
REV
FWD
23
LDI
FWD.REV
FWD
REV
FWD
24
LDO
CMD RUN.STOP
STOP
RUN
STOP
25
LDI
RUN.STOP
STOP
RUN
STOP
26
LDO
HAND AUTO
AUTO
HAND
AUTO
P3.2.2
27
LAO
INPUT REF A
0
PCT
0.01
0
28
LAI
ACT FREQ REF
0
HZ
0.1
-320
M2.2.2
29
LDO
DAY.NGT
DAY
NIGHT
DAY
30
LAI
ANALOG IN 1
0.00
PCT
0.01
0
P5.1.8
31
LAI
ANALOG IN 2
0.00
PCT
0.01
0
P5.1.10
32
LAI
ANALOG OUT 1
0.00
PCT
0.01
0
P5.1.12
33
LDI
DIGITAL IN 1
OFF
ON
OFF
P5.1.1
34
LDI
DIGITAL IN 2
OFF
ON
OFF
P5.1.2
35
LDI
DIGITAL IN 3
OFF
ON
OFF
P5.1.3