Operating Instructions

Chapter 4 - Parameters and Menu Structure
I/O and Hardware (M5)
142 | 187
Siemens Industry, Inc.
Siemens BT300 HVAC Drive
DPD01809
Smart Infrastructure
2019-05-29
Point
Number
Point
Type
Subpoint Name
Factory
Default
Engr. Units
Slope
Intercept
On Text
Off Text
Drive Menu
73
LAO
ANYVALUE
0
1
0
74
LAI
ID VERSION
0
1
0
M4.8.6
75
LAI
AP VERSION
0
1
0
M4.8.7
76
LAO
ACCEL TIME
0
SEC
0.1
0.1
P3.4.2
77
LAO
DECEL TIME
0
SEC
0.1
0.1
P3.4.3
78
LDI
AUTORESET
OFF
ON
OFF
P3.10.1
79
LAI
CURRENT LMT
0
AMPS
0.1
0
P3.1.1.7
80
LDI
ENERGY OPT
OFF
ON
OFF
P3.1.2.18
81
LDI
INTERLOC1
OFF
ON
OFF
P3.5.1.12
82
LDI
INTERLOC2
OFF
ON
OFF
P3.5.1.13
83
LAI
MAX FREQ REF
500
HZ
0.1
0
P3.3.2
84
LAI
MIN FREQ REF
0
HZ
0.1
0
P3.3.1
85
LAI
MOTOR COSPHI
0.01
0.3
P3.1.1.5
86
LAI
MOTOR N CURR
AMPS
0.1
0
P3.1.1.4
87
LAI
MOTOR N PWR
HP
0.134
0
P3.1.1.6
88
LAI
MOTOR N SPD
RPM
1
24
P3.1.1.3
89
LAI
MOTOR N VOLT
VOLTS
1
0
P3.1.1.1
90
LAI
MOTOR N FREQ
HZ
0.01
8
P3.1.1.2
91
LDI
FAULT ACTIVE
NO
Yes
No
92
LAI
FAULT ID
0
1
0
M2.2.18
93
LDO
RESET FAULT
1
0
RESET
NORMAL
94
LAI
BYP ENABLE
1
0
P3.17.4
95
LAI
BYP SAFESTAT
0
1
0
M2.2.28
96
LDI
BYP ACTIVE
OFF
ON
OFF
97
LDI
BYP RUNNING
OFF
ON
OFF
98
LAI
BYP RUN TIME
0
HRS
1
0
M2.2.29
99
LAO
ERROR STATUS
0
1
0
NOTE:
Valid values are 0 through127. Exception is 99; this is a broadcast address and is
reserved. Do not assign an address of 99 to any device on the P1 FLN.