Point
Number
Point
Type
Subpoint Name
Factory
Default
Engr. Units
Slope
Intercept
On Text
Off Text
Drive Menu
73
LAO
ANYVALUE
0
1
0
74
LAI
ID VERSION
0
1
0
M4.8.6
75
LAI
AP VERSION
0
1
0
M4.8.7
76
LAO
ACCEL TIME
0
SEC
0.1
0.1
P3.4.2
77
LAO
DECEL TIME
0
SEC
0.1
0.1
P3.4.3
78
LDI
AUTORESET
OFF
ON
OFF
P3.10.1
79
LAI
CURRENT LMT
0
AMPS
0.1
0
P3.1.1.7
80
LDI
ENERGY OPT
OFF
ON
OFF
P3.1.2.18
81
LDI
INTERLOC1
OFF
ON
OFF
P3.5.1.12
82
LDI
INTERLOC2
OFF
ON
OFF
P3.5.1.13
83
LAI
MAX FREQ REF
500
HZ
0.1
0
P3.3.2
84
LAI
MIN FREQ REF
0
HZ
0.1
0
P3.3.1
85
LAI
MOTOR COSPHI
0.01
0.3
P3.1.1.5
86
LAI
MOTOR N CURR
AMPS
0.1
0
P3.1.1.4
87
LAI
MOTOR N PWR
HP
0.134
0
P3.1.1.6
88
LAI
MOTOR N SPD
RPM
1
24
P3.1.1.3
89
LAI
MOTOR N VOLT
VOLTS
1
0
P3.1.1.1
90
LAI
MOTOR N FREQ
HZ
0.01
8
P3.1.1.2
91
LDI
FAULT ACTIVE
NO
Yes
No
92
LAI
FAULT ID
0
1
0
M2.2.18
93
LDO
RESET FAULT
1
0
RESET
NORMAL
94
LAI
BYP ENABLE
1
0
P3.17.4
95
LAI
BYP SAFESTAT
0
1
0
M2.2.28
96
LDI
BYP ACTIVE
OFF
ON
OFF
97
LDI
BYP RUNNING
OFF
ON
OFF
98
LAI
BYP RUN TIME
0
HRS
1
0
M2.2.29
99
LAO
ERROR STATUS
0
1
0
P1 Control Information
To monitor objects though P1 FLN, complete the following steps:
1. Set Protocol (P5.8.1.1) to a value of P1.
2. Set Slave Address (P5.8.3.1.1) to the desired P1 FLN node number.
NOTE:
Valid values are 0 through127. Exception is 99; this is a broadcast address and is
reserved. Do not assign an address of 99 to any device on the P1 FLN.
3. Set Baud Rate (P5.8.3.1.2) to the desired P1 FLN baud rate.