Operating Instructions

Chapter 4 - Parameters and Menu Structure
I/O and Hardware (M5)
143 | 187
Siemens Industry, Inc.
Siemens BT300 HVAC Drive
DPD01809
Smart Infrastructure
2019-05-29
Structure
Parameter
Unit
Min
Max
Default
ID
Description
Parameters
P5.8.3.1.1
Slave Address
1
247
1
2320
Defines the Modbus RTU unique
device address.
P5.8.3.1.2
Baud Rate
bps
300
230400
6
2378
Defines the communication speed
of the Modbus RTU network.
1 = 300
2 = 600
3 = 1200
4 = 2400
5 = 4800
6 = 9600
7 = 19200
8 = 38400
9 = 57600
10 = 76800
11 = 115200
12 = 230400
P5.8.3.1.3
Parity Type
None
Even
None
2379
Defines the parity type of the
Modbus RTU network:
0 = None
1 = Odd
2 = Even
P5.8.3.1.4
Stopbits
1 Sb
2 Sb
2 Sb
2380
Defines the stop bits of the
Modbus RTU network:
1 = 1 Stop bit
2 = 1.5 Stop bits
3 = 2 Stop bits