Operating Instructions
Chapter 4 - Parameters and Menu Structure
I/O and Hardware (M5)
149 | 187
Siemens Industry, Inc.
Siemens BT300 HVAC Drive
DPD01809
Smart Infrastructure
2019-05-29
Table 112: Defined Modbus Input and Holding Registers.
Register number
Purpose
Access type
See the Table...
0001 - 2000
Siemens Application IDs
16-bit
Parameter IDs [➙ 149]
2001 - 2050
FBProcessDataIN
16-bit
Fieldbus Process Data IN [➙ 149]
2051 - 2099
FBProcessDataIN
32-bit
Fieldbus Process Data IN [➙ 149]
2101 - 2150
FBProcessDataOUT
16-bit
Fieldbus Process Data Out [➙ 150]
2151 - 2199
FBProcessDataOUT
32-bit
Fieldbus Process Data Out [➙ 150]
2200 - 10000
Siemens Application IDs
16-bit
Parameter IDs [➙ 149]
10501 - 10530
IDMap
16-bit
ID Map Initialization [➙ 152]
10601 - 10630
IDMap Read/Write
16-bit
Parameter Values in 16-bit IDMap
Read/Write Registers [➙ 152]
10701 - 10760
IDMap Read/Write
32-bit
Example of Parameter Values in 32-bit
IDMap Read/Write Registers [➙ 153]
20001 -40000
Siemens Application IDs
32-bit
Parameter IDs [➙ 149]
40001 - 40007
Operation day counter
16-bit
Operation Day Counter [➙ 153]
40101 -40107
Resettable operation day counter
16--bit
Resettable Operation Day Counter
[➙ 153]
40201 - 40203
Energy counter
16bit
Energy Counter [➙ 154]
40301 -40303
Resettable energy counter
16-bit
Resettable Energy Counter [➙ 154]
40401 - 40430
Fault history
16-bit
Fault History [➙ 154]
Application IDs
Application IDs are parameters that depend on the frequency converter's application. These parameters can
be read and written by pointing the corresponding memory range directly or by using the so-called ID map. It
is easiest to use a straight address if you want to read a single parameter value or parameters with
consecutive ID numbers. It is possible to read 12 consecutive ID addresses.
Table 113: Modbus Parameter IDs.
Register number
Purpose
Application ID
0001-2000
Application parameters
1 through 2000
2200-10000
Application parameters
2200 through
10000
FB Process data IN
The process data fields are used to control the drive (for example, Run, Stop, Reference, Fault Reset) and to
quickly read actual values (for example, Output frequency, Output current, Fault code). The fields are
structured as follows:
Process Data Master → Slave (max 22 bytes)
Table 114: Fieldbus Process Data IN.
Address
Name
Range/Type
16-bit*
32-bit
2001
2051 = High data
2052 = Low data
FB Control Word
Binary coded
2002
-
Reserved
Binary coded