Operating Instructions
Chapter 4 - Parameters and Menu Structure
I/O and Hardware (M5)
153 | 187
Siemens Industry, Inc.
Siemens BT300 HVAC Drive
DPD01809
Smart Infrastructure
2019-05-29
Example of 32-Bit IDMap
Table 121: Example of Parameter Values in 32-bit IDMap Read/Write Registers.
Address
Data
410701
Data High, parameter ID700
410702
Data Low, parameter ID700
410703
Data High, parameter ID702
410704
Data Low, parameter ID702
Operation Day Counter
Table 122: Operation Day Counter.
Address
Register
Purpose
40001
440001
Years
40002
440002
Days
40003
440003
Hours
40004
440004
Minutes
40005
440005
Seconds
Resettable Operation Day Counter
Reset the counter by writing 1 for Parameter ID2311.
Table 123: Resettable Operation Day Counter.
Address
Register
Purpose
40101
440101
Years
40102
440102
Days
40103
440103
Hours
40104
440104
Minutes
40105
440105
Seconds
Energy Counter
The last number of the Format field indicates the decimal point place in the Energy
field. If the number is
bigger than 0, move the decimal point to the left by the number indicated. For example, Energy = 1200,
Format = 52. Unit = 1. Energy = 12.00 kWh.