Operating Instructions

Chapter 4 - Parameters and Menu Structure
I/O and Hardware (M5)
155 | 187
Siemens Industry, Inc.
Siemens BT300 HVAC Drive
DPD01809
Smart Infrastructure
2019-05-29
ADDRESS
01 hex Slave address 1 hex (= 1)
FUNCTION
10 hex Function 10 hex (= 16)
DATA
Starting address HI
07 hex Starting address 07D0 hex (= 2000)
Starting address LO
D0 hex
No. of registers HI
00 hex
No. of registers LO
03 hex Number of registers 0003 hex (= 3)
Byte count
06 hex Byte count 06 hex (= 6)
Data HI
00 hex Data 1 = 0001 hex (= 1). Setting control word run bit to 1.
Data LO
01 hex
Data HI
00 hex Data 2 = 0000 hex (= 0).
Data LO
00 hex
Data HI
13 hex Data 3 = 1388 hex (= 5000), Speed Reference to 50.00%
Data LO
88 hex
ERROR
CRC HI
C8 hex CRC field C8CB hex (= 51403)
CHECK
CRC LO
CB hex
01
10
07
D0
00
03
06
00
01
00
00
13
88
C8
CB
ADDRESS
01 hex Slave address 1 hex (= 1)
FUNCTION
10 hex Function 10 hex (= 16)
DATA
Starting address HI
07 hex Starting address 07D0 hex (= 2000)
Starting address LO
D0 hex
No. of registers HI
00 hex Number of registers 0003 hex (= 3)
No. of registers LO
03 hex
ERROR
CRC HI
80 hex CRC 8085 hex (= 32901)
CHECK
CRC LO
85 hex
01
10
07
D0
00
03
80
85