Control word (P5.9.2.2.1.10)
Displays the Control Word received from the bus.
Status word (P5.9.2.2.1.11)
Displays the current Status Word that is sent to the bus.
Connection 2
The monitoring values display the same pieces of information as for Connection 1 [➙ 163], for the 2nd and
3rd connections.
Connection 3
The monitoring values display the same pieces of information as for Connection 1 [➙ 163], for the 2nd and
3rd connections.
Quick Setup
For monitoring objects using ModBus TCP, complete the following steps:
NOTICE
The DHCP settings must be set properly. Otherwise, a Fixed IP address may have
to be setup.
If using DHCP, complete the following steps:
1. Select:
Main Menu > I/O and Hardware (M5) > Ethernet (M5.9) > Common settings (M5.9.1) >IP Address
Mode (M5.9.1.1).
2. Verify this is set to
DHCP with AutoIP.
3. Select:
Main Menu > I/O and Hardware (M5) > Ethernet (M5.9) > Common settings (M5.9.1) >IP Address
(M5.9.1.2).
4. Verify that a valid IP Address has been assigned.
If using a Fixed IP address, complete the following:
1. Select:
Main Menu > I/O and Hardware (M5) > Ethernet (M5.9) > Common settings (M5.9.1) >IP Address
Mode (M5.9.1.1) > Edit.
2. Select
Fixed IP.
3. Select:
Main Menu > I/O and Hardware (M5) > Ethernet (M5.9) > Common settings (M5.9.1) >IP Address
(M5.9.1.2) > Edit.
4. Enter desired
IP address.
5. Select:
Main Menu > I/O and Hardware (M5) > Ethernet (M5.9) > Common settings (M5.9.1) >Subnet Mask
(M5.9.1.3) > Edit.