Operating Instructions
Chapter 4 - Parameters and Menu Structure
I/O and Hardware (M5)
165 | 187
Siemens Industry, Inc.
Siemens BT300 HVAC Drive
DPD01809
Smart Infrastructure
2019-05-29
6. Enter the desired
subnet mask.
7. Select:
Main Menu > I/O and Hardware (M5) > Ethernet (M5.9) > Common settings (M5.9.1) >Default
Gateway (M5.9.1.4) > Edit.
8. Enter the desired
default gateway.
For either DHCP or Fixed, the following steps must be completed:
1. Select:
Main Menu > I/O and Hardware (M5) > Ethernet (M5.9) > ModBusTCP (M5.9.2) > Common Settings
(M5.9.2.1) > Connection Limit (M5.9.2.1.1) > Edit.
2. Select the desired connection limit.
3. Select:
Main Menu > I/O and Hardware (M5) > Ethernet (M5.9) > ModbusTCP (M5.9.2) > Common Settings
(M5.9.2.1) > Slave Address (M5.9.2.1.2) > Edit.
4. Enter the desired address.
For commanding Run/Stop using BACnet/IP complete the following steps (in addition
to the Monitoring steps above):
1. Select:
Main Menu > Quick Setup (M1) > Ctrl. Place Auto (M1.15) > Edit.
2. Select
FieldBusCTRL
For commanding of Speed Reference using BACnet/IP complete the following steps
(in addition to the monitoring steps above):
1. Select:
Main Menu > Quick Setup (M1) > I/O A Ctrl Ref (M1.10) > Edit.
2. Select
Fieldbus.
BACnet IP (M5.9.3)
BACnet IP Parameters and Monitoring Values
Ethernet Common Settings (M5.9.1)
Table 131: Common Settings for BACnet/IP.
Code
Parameter
Min
Max
Unit
Default
ID
Description
P5.9.1.1
IP address mode
See
Ethernet common settings
.
P5.9.1.3
IP address
See
Ethernet common settings
.
P5.9.1.4
Subnet mask
See
Ethernet common settings
.
P5.9.1.5
Default gateway
See
Ethernet common settings
.
P5.9.1.6
MAC address
See
Ethernet common settings
.