Operating Instructions

Chapter 4 - Parameters and Menu Structure
I/O and Hardware (M5)
166 | 187
Siemens Industry, Inc.
Siemens BT300 HVAC Drive
DPD01809
Smart Infrastructure
2019-05-29
Code
Parameter
Min
Max
Unit
Default
ID
Description
P5.9.3.1.1
Instance number
0
4194304
0
2406
Device object’s instance number
0 = Serial number
P5.9.3.1.2
Communication time-
out
0
65535
m
0
2407
0 = Not used
NOTE: This setting is in
minutes.
P5.9.3.1.3
Protocol in use
0
1
0
2408
0 = Not used
1 = Used
P5.9.3.1.4
BBMD OP
0.0.0.1
255.255.2
55.255
192.168.0.1
2409
Network BBMD IP address.
P5.9.3.1.5
BBMD Port
1
65535
47808
2410
BBMD UDP Port number.
P5.9.3.1.6
Time to live
0
255
0
2411
Code
Parameter
Min
Max
Unit
Default
ID
Description
M5.9.3.2.1
Fieldbus protocol
status
1
3
1 = Stopped
2 = Operational
3 = Faulted
M5.9.3.2.2
Communication status
0.0
99.999
0.0
0-99 Number of messages with
errors.
0-999 Number of messages
without communication errors.
M5.9.3.2.3
Actual instance number
0
65535
Serial
number
Shows actual Device Object's
instance number.
M5.9.3.2.4
Control word
hex
See
IP monitoring values.
M5.9.3.2.5
Status word
hex
See
IP monitoring values.