Operating Instructions
Chapter 4 - Parameters and Menu Structure
I/O and Hardware (M5)
168 | 187
Siemens Industry, Inc.
Siemens BT300 HVAC Drive
DPD01809
Smart Infrastructure
2019-05-29
Quick Setup
For monitoring objects using BACnet IP, complete the following steps:
NOTICE
The DHCP settings must be set properly. Otherwise, a Fixed IP address may have
to be set up.
If using DHCP, complete the following steps:
1. Select:
Main Menu > I/O and Hardware (M5) > Ethernet (M5.9) > Common settings (M5.9.1) >IP Address
Mode (M5.9.1.1).
2. Verify this is set to
DHCP with AutoIP.
3. Select:
Main Menu > I/O and Hardware (M5) > Ethernet (M5.9) > Common settings (M5.9.1) >IP Address
(M5.9.1.2).
4. Verify that a valid IP Address has been assigned.
If using a Fixed IP address, complete the following steps:
1. Select:
Main Menu > I/O and Hardware (M5) > Ethernet (M5.9) > Common settings (M5.9.1) >IP Address
Mode (M5.9.1.1) > Edit.
2. Select
Fixed IP.
3. Select:
Main Menu > I/O and Hardware (M5) > Ethernet (M5.9) > Common settings (M5.9.1) >IP Address
(M5.9.1.2) > Edit.
4. Enter the desired
IP address.
5. Select:
Main Menu > I/O and Hardware (M5) > Ethernet (M5.9) > Common settings (M5.9.1) >Subnet Mask
(M5.9.1.3) > Edit.
6. Enter the desired
subnet mask.
7. Select:
Main Menu > I/O and Hardware (M5) > Ethernet (M5.9) > Common settings (M5.9.1) >Default
Gateway (M5.9.1.4) > Edit.
8. Enter the desired
default gateway.
For either DHCP or Fixed, the following steps must be completed:
1. Select:
Main Menu > I/O and Hardware (M5) > Ethernet (M5.9) > BACnet IP (M5.9.3) > Settings
(M5.9.3.1) > Instance Number (M5.9.3.1.1) > Edit.
2. Select desired
device instance number.