Operating Instructions

Chapter 4 - Parameters and Menu Structure
Favorites (M7)
170 | 187
Siemens Industry, Inc.
Siemens BT300 HVAC Drive
DPD01809
Smart Infrastructure
2019-05-29
Structure
Parameter
ID
Description
P6.5.1
Restore Factory
Default
831
Activation parameter for restoring parameters to the factory settings.
NOTE: Does not reset: Time (P5.5.2), Date (P5.5.3), Year (P5.5.4), Daylight Saving
(P5.5.5)
P6.5.2
Save to Keypad
2487
Initiates a copy of the active set of parameters to the keypad's storage location.
P6.5.3
Restore from Keypad
2488
Initiates a copy of the keypad's storage location to the active set of parameters.
P6.5.4
Save to Set 1
2489
Initiates a copy of the active set of parameters to the drives set 1 storage location.
P6.5.5
Restore from Set 1
2490
Initiates a copy of the drives set 1 storage location to the active set of parameters.
P6.5.6
Save to Set 2
2491
Initiates a copy of the active set of parameters to the drives set 2 storage location.
P6.5.7
Restore from Set 2
2492
Initiates a copy of the drives set 2 storage location to the active set of parameters.
Structure
Parameter
ID
Description
P6.6.1
Active Set-Set 1
2493
Initiates a compare of the drive‘s active parameter set to the saved set 1. All
parameters that are different are displayed, with values.
P6.6.2
Active Set-Set 2
2494
Initiates a compare of the drive‘s active parameter set to the saved set 2. All
parameters that are different are displayed, with values.
P6.6.3
Active Set-Defaults
2495
Initiates a compare of the drive‘s active parameter set to the default values. All
parameters that are different are displayed, with values.
P6.6.4
Active Set-Keypad Se
2496
Initiates a compare of the drive‘s active parameter set to the keypad saved set.
All parameters that are different are displayed, with values.