Operating Instructions
Chapter 4 - Parameters and Menu Structure
User Levels (M8)
171 | 187
Siemens Industry, Inc.
Siemens BT300 HVAC Drive
DPD01809
Smart Infrastructure
2019-05-29
1. Set Access Code (P8.2) to a value other than 0.
NOTE:
Store this access code in a safe place. If the code is lost, the only method to
recover is to reload firmware and re-commission the drive.
2. Set User Level (P8.1) to a value of Monitoring.
When in the monitoring user level, only the Monitor (M2), Favorites (M7), and User Levels (M8) menu options
are available through the keypad.
To switch back to Normal mode, complete the following steps:
1. Set User Level (P8.1) to a value of Normal.
2. When prompted for Access Code (P8.2), enter the value previously entered when locking the key-pad.
Table 137: User Level Settings.
Structure
Parameter
Unit
Min
Max
Default
ID
Description
P8.1
User Level
Normal
Monitoring
Normal
1194
Defines the user level mode of the
keypad.
0 = Normal = All menus are
available.
1 = Monitoring = Only the Monitor
(M2), Favorites (M7), and User
Levels (M8) menus are available.
P8.2
Access Code
0
99999
0
2362
Defines the access code to be
used when switching User Level
(P8.1).