Operating Instructions

Chapter 3 - Start-up Information
Procedure and Checklist
21 | 187
Siemens Industry, Inc.
Siemens BT300 HVAC Drive
DPD01809
Smart Infrastructure
2019-05-29
There are several pre-checks that should be completed prior to powering up and commissioning
the BT300 HVAC Drive. See
the BT300 Startup Procedure and Checklist
(125-1006) for more
details.
This step should be completed on all drives at start-up to ensure a good, known starting point.
Select: User Settings (M6) > Parameter Backup (M6.5) > Restore Factory Defaults (P6.5.1).
This step should be completed on all drives at start-up. This will be automatically started at the
end of the Factory Reset. Select: Quick Setup > Startup Wizard (P1.19), if necessary.
If any other wizards are needed, select one of the following:
Quick Setup > PID Mini-Wizard (M1.17) > Quick Setup/Multi-Pump Wizard (M1.20)
Quick Setup > Startup Wizard (M1.19) > Quick Setup/Fire Mode Wizard (M1.20)
Quick Setup > Bypass Wizard (M1.21)
Any other application-specific settings should be completed at this time.
Even if enabled during the Startup Wizard, the Auto-Reset should be configured for the site’s
requirements. There are several parameters to configure in this menu. Review all parameters.
Select: Parameters (M3) > Automatic Reset (M3.10)
This forces the Monitor, Favorites, and User Level menus only. This prevents unauthorized
parameterization through the keypad.
Select: User Levels (M8) > Access Code (P8.2). Set to desired access code (such as 4521).
User Levels (M8)/User Level (P8.1). Set to Monitoring.
To return to edit menus, select: User Levels (M8) > User Level (P8.1), and set to Normal. Enter
the Access code when prompted.