Step
Parameter/Question
Settings
21
Start Function (P3.2.4)
Defines the start function of the drive.
0 = Ramping Start
1 = Flying Start
22
Stop Function (P3.2.5)
Defines the stop function of the drive.
0 = Coast to Stop
1 = Ramping Stop
23
Motor Switch (P3.1.2.2)
Prevents the drive from tripping when a motor switch is located
between the drive and motor.
0 = No
1 = Yes
24
Bypass Wizard (P1.21)
Enable parameter for the Bypass Wizard. This wizard can be
activated during the Startup Wizard.
Step
Parameter/Question
Settings
1
Process unit selection (P3.12.1.4)
Several selections, see P3.12.1.4.
Step
Parameter/Question
Settings
2
Process Unit Min (P3.12.1.5)
Varies
3
Process Unit Max (P3.12.1.6)
Varies
4
Process Unit Decimals (P3.12.1.7)
Range: 0 to 4
5
Feedback 1 Source Selection (P3.12.3.3)
Several selections, see P3.12.3.3.
Step
Parameter/Question
Settings
6
Analog Input Signal Range
0 to 10V/0 to 20 mA
2 to 10V/4 to 20 mA
7
Error Inversion (P3.12.1.8)
Reverse Acting
Direct Acting
8
Setpoint Source Selection (P3.12.2.4)
Several selections, see P3.12.3.4.