Operating Instructions
Chapter 3 - Start-up Information
Wizards
25 | 187
Siemens Industry, Inc.
Siemens BT300 HVAC Drive
DPD01809
Smart Infrastructure
2019-05-29
Step
Parameter/Question
Settings
9
Analog Input Signal Range
0 to 10V/0 to 20 mA
2 to 10V/4 to 20 mA
10
Keypad SP1 (P3.12.2.1) or Keypad SP2
(P3.12.2.2)
Varies
11
Sleep Function?
No
Yes
If the option Yes is selected for Sleep Function, you will be prompted for the sleep function settings:
Step
Parameter/Question
Settings
12
Sleep Frequency Limit 1 (P3.13.2.7)
Varies
13
Sleep Delay 1 (P3.12.2.8)
Varies
14
Wake-up Level 1 (P3.12.2.9)
Varies
The PID Mini-Wizard is now complete.
Multi-Pump Wizard (P1.18)
The Multi-Pump Wizard is activated in the Quick Setup (M1) menu. This wizard assists with configuring the
drive for use with PID Controller 1, and then asks the most important questions for setting up a multi-pump
system.
The following steps are required to successfully complete the Multi-Pump Wizard:
Step
Parameter/Question
Settings
1 – 14
Same as PID Mini-Wizard
15
Number of Motors (P3.14.1)
1 to 4
16
Interlock Function (P3.14.2)
Not Used
Enabled
17
Auto-change (P3.14.4)
Disabled
Enabled
If the Auto-change function is enabled, the following will display. Otherwise, the wizard jumps directly to Step
21:
Step
Parameter/Question
Settings
18
Include FC (P3.14.3)
Disabled
Enabled
19
Auto-change Interval (P3.14.5)
0.0 to 3000.0 h
20
Auto-change Frequency Limit (P3.14.6)
0.0 to 60.0 Hz
21
Bandwidth (P3.14.8)
0 to 100%
22
Bandwidth Delay (P3.14.9)
0 to 3600 s
After this, the keypad displays the digital input and relay output configuration done by the application. It is
recommended that these values are written down for future reference.
The Multi-Pump Wizard is now complete.