Siemens BT300 HVAC Drive
DPD01809
Smart Infrastructure
2019-05-29
NOTE:
The warranty is void if the Fire Mode function is activated. Test Mode can be used
to test the Fire Mode function without voiding the warranty. Read important
information about the password and warranty issues in Chapter 4 before you
proceed.
Step
Parameter/Question
Settings
1
Fire Mode Frequency Source (P3.16.5)
Several selections; see P3.16.5.
Step
Parameter/Question
Settings
2
Fire Mode Frequency (P3.16.4)
Range: 0 to Maximum Frequency (P1.9)
3
Signal Activation?
Open Contact
Closed Contact
4
Fire Mode Activation Open (P3.16.2)
Or
Fire Mode Activation Close (P3.16.3)
Choose the digital input to activate Fire Mode.
5
Fire Mode Reverse (P3.16.6)
Choose the digital input to activate the reverse command
in Fire Mode.
DigIN Slot0.1 = FORWARD
DigIN Slot0.2 = REVERSE
6
Fire Mode Password (P3.16.1)
Choose the password to enable the Fire Mode Function.:
1234 = Test Mode
1002 = Enable Fire Mode