Operating Instructions

Chapter 4 - Parameters and Menu Structure
Monitor Menu (M2)
31 | 187
Siemens Industry, Inc.
Siemens BT300 HVAC Drive
DPD01809
Smart Infrastructure
2019-05-29
Structure
Parameter
Unit
ID
Description
P1.14
Decel Time 1
s
104
Time allowed for motor to decelerate from Maximum Frequency (P1.9) to
a standstill (0). Also see
Menu Structure
P3.4.3
.
P1.15
Ctrl. Place Auto
172
Start/Stop commands are given differently depending upon the control
place. This parameter defines whether the Start/Stop command is
controlled by digital inputs as defined in Control Signal 1 A (P3.5.1.1) and
Control Signal 2 A (P3.5.1.2) in accordance with the I/O A Start/Stop
Logic (P3.2.6) or if the Start/Stop command is controlled by the Fieldbus
that is in use.
Settings:
0 = I/O Control (control is from the physical I/O, PID control, or time
channels)
1 = Fieldbus (control is from the configured fieldbus found in Ethernet or
RS-485 settings)
Also see
Menu Structure
P3.2.1
.
P1.16
Automatic Reset
731
Enable parameter for the Automatic Reset function of the drive. This
feature is configured in the Parameters (M3) Automatic Reset
(M3.10) menu.
Also see
Menu Structure
P3.10.1
.
P1.17
PID Mini-Wizard
1803
Enable parameter for the PID Mini-Wizard. This wizard assists with the
configuration of the PID Controller 1 using a single feedback and single
setpoint.
P1.18
MultiPump Wizard
Enable parameter for the Multi-Pump Wizard. This wizard assists with the
configuration of the Multi-Pump function of the drive. The PID Mini Wizard
will precede this wizard.
P1.19
Startup Wizard
1171
Enable parameter for the Startup Wizard. This wizard assist with the
essential information required for drive operation.
This wizard is automatically enabled after Restore Factory Defaults
(P6.5.1) is activated.
P1.20
Fire Mode Wizard
1672
Enable parameter for the Fire Mode Wizard.
P1.21
Bypass Wizard
1823
Enable parameter for the Bypass Wizard. This wizard can be activated
during the Startup Wizard.
Menu and Parameter Group
Description
Multimonitor (M2.1)
Display of 9 monitored values.
Basic (M2.2)
Display of basic drive monitoring parameters.
Timer Functions (M2.3)
Display of timer function specific monitoring parameters.
PID Controller 1 (M2.4)
Display of PID Controller 1 specific monitoring parameters.
PID Controller 2 (M2.5)
Display of PID Controller 2 specific monitoring parameters.
Multi-Pump (M2.6)
Display of Multi-Pump specific monitoring parameters.
Fieldbus Data (M2.8)
Display of Mapped Fieldbus Data monitoring parameters.
Temp. Inputs (M2.9)
Display of connected temperature inputs.