Operating Instructions

Chapter 4 - Parameters and Menu Structure
Monitor Menu (M2)
33 | 187
Siemens Industry, Inc.
Siemens BT300 HVAC Drive
DPD01809
Smart Infrastructure
2019-05-29
Structure
Parameter
Unit
ID
Description
M2.2.17
DriveStatusWord
43
Bit coded status of the drive
B1 = Ready
B2 = Run
B3 = Fault
B6 = Run Enable
B7 = Alarm Active
B10 = DC Current (in stop)
B11 = DC Brake Active
B12 = Run Request
B13 = Motor Regulator Active
M2.2.18
Last ActiveFault
37
Fault code of last activated fault that has not been reset.
See Fault Codes
.
M2.2.19
FireMode Status
1597
0 = Disabled
1 = Enabled
2 = Activated (Enabled & DI)
3 = Test Mode
M2.2.20
DIN StatusWord1
56
B0 = SlotA.1…B5 = SlotA.6
B6 = SlotB.1…B11 = SlotB.6
B12 = SlotC.1…B15 = SlotC.4
M2.2.21
DIN StatusWord2
57
B0 = SlotC.5…B1 = SlotC.6
B2 = SlotD.1…B7 = SlotD.6
B8 = SlotE.1…B13 = SlotE.4
M2.2.22
MotCurrent1Deci.
45
Motor current monitor value with fixed number of decimals and less filtering.
For example, can be used for fieldbus purpose to always get the right value
regardless of frame size, or monitoring when less filtering time is needed for
motor current.
M2.2.23
Appl.StatusWord1
89
Bit coded application status word 1
B0 = Interlock1
B1 = Interlock2
B5 = I/O A Control Active
B6 = I/O B Control Active
B7 = Fieldbus Control Active
B8 = Hand Control Active
B9 = PC Control Active
B10 = Preset Freq Active
B12 = FireMode Active
B13 = PreHeat Active
M2.2.24
Appl.StatusWord2
90
Bit coded application status word 2
B0 = Acc/Dec Prohibited
B1 = MotorSwitch Active
M2.2.25
kWhTripCounter Low
1054
Energy counter with kWh output (low word)
M2.2.26
kWhTripCounter High
1067
# of times energy counter has spun around (high word)
M2.2.27
Appl.StatusWord3
1851
Bit coded application status word 3
M2.2.28
Safety StatusWord
1852
Bit coded Safety Status Word
M2.2.29
Bypass Runtime
h
1850
Bypass Running Hours