Operating Instructions

Chapter 4 - Parameters and Menu Structure
Parameters (M3)
38 | 187
Siemens Industry, Inc.
Siemens BT300 HVAC Drive
DPD01809
Smart Infrastructure
2019-05-29
Structure
Parameter
Unit
Min
Max
Default
ID
Description
P3.1.1.1
Motor Nom Voltg
V
Varies
Varies
Varies
110
Defines nominal motor voltage
from motor nameplate data.
Also
see Menu Structure P1.1.
P3.1.1.2
Motor Nom Freq
Hz
8
320
60
111
Defines nominal motor frequency
from motor nameplate data. Also
see
Menu Structure P1.2.
P3.1.1.3
Motor Nom Speed
rpm
24
19200
Varies
112
Defines nominal motor speed
from motor nameplate data. Also
see
Menu Structure P1.3.
P3.1.1.4
Motor Nom Currnt
A
Varies
Varies
Varies
113
Defines nominal motor current
from motor nameplate data. Also
see
Menu Structure P1.4.
P3.1.1.5
Motor Cos Phi
0.3
1
Varies
120
Defines nominal motor Cos Phi
(power factor) from motor
nameplate data. Also see
Menu
Structure P1.5.
P3.1.1.6
Motor Nom Power
hp
Varies
Varies
Varies
116
Defines nominal motor power
from motor nameplate data. Also
see
Menu Structure P1.6.
P3.1.1.7
Current Limit
A
Varies
Varies
Varies
107
Defines maximum current limit for
motor. Suggested to use Motor
Nominal Current (P3.1.1.4)
multiplied by motor service factor
from motor nameplate data.
Also
see
Menu Structure P1.7.
P3.1.1.8
Motor Type
IM
PMM
IM
650
Selection of the motor type as
follows:
0 = IM = Asynchronous Induction
Motor
1 = PMM = PM Synchronous
Motor