Operating Instructions

Chapter 4 - Parameters and Menu Structure
Parameters (M3)
41 | 187
Siemens Industry, Inc.
Siemens BT300 HVAC Drive
DPD01809
Smart Infrastructure
2019-05-29
Structure
Parameter
Unit
Min
Max
Default
ID
Description
P3.2.1
Ctrl. Place Auto
I/O Control
Fieldbus Ctrl
I/O
Control
172
Start/Stop commands are given
differently depending upon the
control place. This parameter
defines whether the Start/Stop
command is controlled by digital
inputs as defined in Control
Signal 1 A (P3.5.1.1) and Control
Signal 2 A (P3.5.1.2) in
accordance with the I/O A
Start/Stop Logic (P3.2.6) or if the
Start/Stop command is controlled
by the fieldbus that is in use.
Settings:
0 = I/O Control
(control is from
the physical I/O, PID control, or
time channels)
1 = Fieldbus
(control is from the
configured fieldbus found in
Ethernet or RS-485 settings)
P3.2.2
Hand/Auto
Auto
Hand
Auto
211
Defines the operational mode of
the unit.
0 = Auto (controlled with I/O or
fieldbus)
1 = Hand (controlled with keypad)
P3.2.3
KeypadStopButton
No
Yes
No
114
Defines the operational status of
the keypad stop button as follows:
0 = No (stop button is not
functional in all control places)
1 = Yes (stop button functions in
all control places)
P3.2.4
Start Function
Ramping
Flying Start
Varies
505
Defines the start function of the
drive.
0 = Ramping Start
1 = Flying Start