Operating Instructions

Chapter 4 - Parameters and Menu Structure
Parameters (M3)
42 | 187
Siemens Industry, Inc.
Siemens BT300 HVAC Drive
DPD01809
Smart Infrastructure
2019-05-29
Structure
Parameter
Unit
Min
Max
Default
ID
Description
P3.2.5
Stop Function
Coasting
Ramping
Coasting
506
Defines the stop function of the
drive.
0 = Coast to Stop
1 = Ramping Stop
P3.2.6
I/O A Logic
Forw-Back
Start-Rev
(edge)
Forw-
Back
300
See
I/O Table.
P3.2.7
I/O B Logic
Forw-Back
Start-Rev
(edge)
Forw-
Back
363
Same as I/O A Logic (P3.2.6). I/O
B Ctrl Force (P3.5.1.5) is used to
determine when this logic is
followed.
P3.2.8
FB Start Logic
Rising edge
State
Rising
Edge
889
Defines the start logic when Ctrl.
Place Auto (P3.2.1) is set to
FieldbusCTRL.:
0 = Rising edge required
1 = State
P3.2.9
Start Delay
Disabled
Enabled
Disabled
14063
Enable parameter for a delayed
start. If enabled, the drive will not
start when a start is active until
the amount of time defined in
Start Delay Time (P3.2.10) has
passed.
P3.2.10
Start Delay Time
s
0
320
0
14064
Defines the delay time before the
drive will start after command is
issued. Start Delay (P3.2.9) must
be enabled.
P3.2.11
Mot. Interlock Start
Disabled
Enabled
Disabled
1811
Enable point for the interlock
application. If enabled, the drive
will energized the relay output
defined for DmprIntlckLogic
when a start is active. The drive
will not start until Run Interlock 1
(P3.5.1.12) and Run Interlock 2
(P3.5.1.13) become active if Mot.
InterlockTimeout (P3.1.12) is set
to 0. Otherwise will activate after
the time defined in Mot.
InterlockTimeout (P3.1.12)
P3.2.12
Mot. InterlockTimeout
s
0
120
0
1816
Defines the amount of time the
drive will wait for the interlock
feedback to be given before
starting.
0 = No timeout time used. Unit
will wait indefinitely for the
feedback before starting the drive.
> 0 = Unit will only wait this time
for the feedback, then start the
drive.
P3.2.13
Run Interlock Proof
14060
Defines the run interlock proof
timeout time. If Run Interlock 1
(P3.5.1.12) or Run Interlock 2
(P3.5.1.13) do not activate within
the time defined, the response
action defined in Run Interlock
Fault (P3.9.29) will occur. This
requires Mot. Interlock Start
(P3.2.11) to be enabled.