Operating Instructions

Chapter 4 - Parameters and Menu Structure
Parameters (M3)
43 | 187
Siemens Industry, Inc.
Siemens BT300 HVAC Drive
DPD01809
Smart Infrastructure
2019-05-29
Selection
Name
Description
0
Ramping
After the Start command, the speed of the motor is accelerated according to the set
acceleration parameters to frequency setpoint.
1
Flying Start
After the Start command, the drive quickly adjusts the output frequency until the actual motor
speed has been found. Then the motor ramps to the frequency setpoint.
Selection
number
Selection name
Description
0
Coasting
The motor is allowed to stop on its own inertia. The control by the drive is discontinued and the
drive current drops to zero as soon as the stop command is given.
1
Ramp
After the Stop command, the speed of the motor is decelerated according to the set deceleration
parameters to zero speed.
Logic
Operation Description
0
Ctrl Signal 1 A (P3.5.1.1) = Start Forward
Ctrl Signal 2 A (P3.5.1.2)= Start Reverse
Ctrl Signal 1 B (P3.5.1.3) = Start Forward
Ctrl Signal 2 B (P3.5.1.4) = Start Reverse
1
Ctrl Signal 1 A (P3.5.1.1) = Start Forward (Edge)
Ctrl Signal 2 A (P3.5.1.2) = Start Reverse (Edge
Ctrl Signal 1 B (P3.5.1.3) = Inverted Stop
Ctrl Signal 2 B (P3.5.1.4) = Inverted Stop
2
Ctrl Signal 1 A (3.5.1.1) = Forward (Edge)
Ctrl Signal 2 A (3.5.1.2) = Backward (Edge)
Ctrl Signal 1 B (3.5.1.3) = Forward (Edge)
Ctrl Signal 2 B (3.5.1.4) = Backward (Edge)
3
Ctrl Signal 1 A (P3.5.1.1) = Start
Ctrl Signal 2 A (P3.5.1.2) = Reverse
Ctrl Signal 1 B (P3.5.1.3) = Start
Ctrl Signal 2 B (P3.5.1.4) = Reverse
4
Ctrl Signal 1 A (P3.5.1.1) = Start (Edge)
Ctrl Signal 2 A (P3.5.1.2) = Reverse
Ctrl Signal 1 B (P3.5.1.3) = Start (Edge)
Ctrl Signal 2 B (P3.5.1.4) = Reverse