2019-05-29
Control reference settings (M3.3)
The frequency reference source is programmable for all control places except the computer, which always
takes the reference from the PC tool.
Auto Control Place I/O A: The source of frequency reference can be selected with I/O Control Reference A
Selection (P3.3.3). The I/O B Reference Force (P3.5.1.6) will determine when the I/O Control Reference B is
in use.
Auto Control Place I/O B: The source of frequency reference can be selected with I/O Control Reference B
Selection (P3.3.4). The I/O B Reference Force (P3.5.1.6) will determine when the I/O Control Reference B is
in use.
Keypad (Hand) Control Place: The source of the frequency reference can be selected with Keypad Control
Reference Selection (P3.3.5). If set to a value of Keypad Reference; then the keypad buttons or Keypad
Reference (P3.3.6) can be used to set the frequency reference.
Fieldbus Control Place: The source of the frequency reference can be selected with Fieldbus Control
Reference Selection (P3.3.9).
Table 26: Control Reference Settings.
Structure
Parameter
Unit
Min
Max
Default
ID
Description
P3.3.1
Min Frequency
Hz
0
Parameter P3.3.2
0
101
Minimum allowed frequency
reference
P3.3.2
Max Frequency
Hz
Parameter
P3.3.1
320
60
102
Maximum allowed frequency
reference
P3.3.3
I/O A Ctrl Ref
PresetFreq0
Motor Pot Ref
AI1 + AI2
117
Selects location of frequency
setpoint source when in I/O A
control. In the following list of
possible settings, the main setpoint
is selected:
1 = Preset Freq 0
2 = Keypad Reference
3 = Fieldbus
4 = AI1
5 = AI2
6 = AI1+AI2
7 = PID 1 Reference
8 = Motor Potentiometer
Also see M1.10.
P3.3.4
I/O B Ctrl Ref
PresetFreq0
Motor Pot Ref
AI1
131
Selects location of frequency
setpoint source when in I/O B
control. In the following list of
possible settings, the main setpoint
is selected:
1 = Preset Freq 0
2 = Keypad Reference
3 = Fieldbus
4 = AI1
5 = AI2
6 = AI1+AI2
7 = PID 1 Reference
8 = Motor Potentiometer
I/O B Ref Force (P3.5.1.6) is used
to determine when this reference is
to be followed.