Operating Instructions

Chapter 4 - Parameters and Menu Structure
Parameters (M3)
53 | 187
Siemens Industry, Inc.
Siemens BT300 HVAC Drive
DPD01809
Smart Infrastructure
2019-05-29
Structure
Parameter
Unit
Min
Max
Default
ID
Description
P3.3.15
Preset Freq 4
Hz
Parameter
P1.8 or
P3.3.1
Parameter
P1.9 or P3.3.2
25
127
Defines the frequency to be used
when the following occurs:
1. PresetFreqMode (P3.3.10) is set
to Binary Coded &
Preset Freq Sel0 (P3.5.1.15) is de-
activated.
Preset Freq Sel1 (P3.5.1.16) is de-
activated.
Preset Freq Sel2 (P3.5.1.17) is
activated.
P3.3.16
Preset Freq 5
Hz
Parameter
P1.8 or
P3.3.1
Parameter
P1.9 or P3.3.2
30
128
Defines the frequency to be used
when the following occurs:
1. PresetFreqMode (P3.3.10) is set
to Binary Coded &
Preset Freq Sel0 (P3.5.1.15) is
activated.
Preset Freq Sel1 (P3.5.1.16) is de-
activated.
Preset Freq Sel2 (P3.5.1.17) is
activated.
P3.3.17
Preset Freq 6
Hz
Parameter
1.8 or P3.3.1
Parameter
1.9 or P3.3.2
40
129
Defines the frequency to be used
when the following occurs:
1. PresetFreqMode (P3.3.10) is set
to Binary Coded &
Preset Freq Sel0 (P3.5.1.15) is de-
activated.
Preset Freq Sel1 (P3.5.1.16) is
activated.
Preset Freq Sel2 (P3.5.1.17) is
activated.
P3.3.18
Preset Freq 7
Hz
Parameter
P1.8 or
P3.3.1
Parameter
P1.9 or P3.3.2
50
130
Defines the frequency to be used
when the following occurs:
1. PresetFreqMode (P3.3.10) is set
to Binary Coded &
Preset Freq Sel0 (P3.5.1.15) is
activated.
Preset Freq Sel1 (P3.5.1.16) is
activated.
Preset Freq Sel2 (P3.5.1.17) is
activated.
P3.3.19
PresetAlarmFreq
Hz
Parameter
P1.8 or
P3.3.1
Parameter
P1.9 or P3.3.2
25
183
Defines the frequency to be
followed when fault responses
(found in Protections [P3.9]) are
defined for Alarm + Preset Freq.
AI Low Fault (P3.9.1)
FieldbusComm Flt (P3.9.19)
P3.3.20
MotPot Ramp
Time
Hz/s
0.1
500
10
331
Rate of change in the motor
potentiometer reference when
increased or decreased.
P3.3.21
MotPot Reset
No Reset
Powered down
Stop State
367
Motor potentiometer frequency
reference reset logic
0 = No Reset
1 = Reset if stop state
2 = Reset if powered down