Operating Instructions

Chapter 4 - Parameters and Menu Structure
Parameters (M3)
55 | 187
Siemens Industry, Inc.
Siemens BT300 HVAC Drive
DPD01809
Smart Infrastructure
2019-05-29
Required Action
For use with 1/O Control Reference (P3.3.3), Preset Freg0 is selected.
Activated Frequency
Preset Frequency 0 (P3.3.11)
B2 (P3.5.1.17)
B1 (P3.5.1.16)
B0 (P3.5.1.15)
Off
Off
On
Preset Frequency 1 (P3.3.12)
Off
On
Off
Preset Frequency 2 (P3.3.13)
Off
On
On
Preset Frequency 3 (P3.3.14)
On
Off
Off
Preset Frequency 4 (P3.3.15)
On
Off
On
Preset Frequency 5 (P3.3.16)
On
On
Off
Preset Frequency 6 (P3.3.17)
On
On
On
Preset Frequency 7 (P3.3.18)
Required Action
For use with 1/O Control Reference (P3.3.3), Preset Freq0 is selected.
Activated Frequency
Preset Frequency 0 (P3.3.11)
B2 (P3.5.1.17)
B1 (P3.5.1.16)
B0 (P3.5.1.15)
Off
Off
On
Preset Frequency 1 (P3.3.12)
Off
On
Off
Preset Frequency 2 (P3.3.13)
On
Off
On
Preset Frequency 3 (P3.3.14)
NOTE:
Ramp 2 always has higher priority and is used if a digital input for Accel/Decel
Time Selection (P.5.1.33) is activated.