Operating Instructions

Chapter 4 - Parameters and Menu Structure
Parameters (M3)
61 | 187
Siemens Industry, Inc.
Siemens BT300 HVAC Drive
DPD01809
Smart Infrastructure
2019-05-29
Structure
Parameter
Default
ID
Description
P3.5.1.28
Interlock 3
DigIN Slot0.1
428
Defines the location for the interlock feedback for motor 3 when
using the multi-pump feature.
P3.5.1.29
Interlock 4
DigIN Slot0.1
429
Defines the location for the interlock feedback for motor 4 when
using the multi-pump feature.
P3.5.1.30
Interlock 5
DigIN Slot0.1
430
Defines the location for the interlock feedback for motor 5 when
using the multi-pump feature.
P3.5.1.31
MotPot UP
DigIN Slot0.1
418
Defines the location for the motor potentiometer reference that
will be used to increase the speed.
Contact closure = increase speed setpoint.
P3.5.1.32
MotPot Down
DigIN Slot0.1
417
Defines the location for the motor potentiometer reference that
will be used to decrease the speed
Contact closure = decrease speed setpoint
P3.5.1.33
Acc/Dec Time Sel
DigIN Slot0.1
408
Defines the location for accel/decel time selection.
Open Contact = Ramp 1 shape (P3.4.1), Accel1 (P3.4.2), and
Decel1 (P3.4.3) to be followed
Contact Closure = Ramp 2 shape (P3.4.4), Accel2 (P3.4.5), and
Decel 2 (P3.4.6) to be followed
P3.5.1.34
Fieldbus Ctrl
DigIN Slot0.1
411
Defines the location to force control place to fieldbus.
Open Contact = I/O Control
Contact closure = Fieldbus Control
P3.5.1.39
FireMode Activ.Open
DigIN Slot0.2
1569
Defines location of fire mode activation on contact opening.
Open Contact = Fire Mode Active
Contact Closure = No Action
Also see Menu Structure P3.16.2.
P3.5.1.40
FireMode Activ.Close
DigIN Slot0.1
1619
Defines location of fire mode activation on contact closing.
Open Contact = No Action
Contact Closure = Fire Mode Active
Also see Menu Structure P3.16.3.
P3.5.1.41
FireMode Reverse
DigIN Slot0.1
1618
Defines location of the reverse command when fire mode is
active as defined by FireMode Activ.Open (P3.16.2) or
FireMode Activ.Close (P3.16.3).
Open Contact = Forward
Contact Closure = Reverse
NOTE: This function has no effect in normal mode of operation.
Also see Menu Structure P3.16.6.
P3.5.1.42
Keypad CTRL
DigIN Slot0.1
410
Defines the location monitored to force the Control Place to
Keypad.
P3.5.1.43
Reset kWh Counter
DigIN Slot0.1
1053
Defines the location of the kWh trip counter reset.
P3.5.1.44
Remote Safety 1*
DigIN SlotA.2
1814
Defines the location of the remote safety.
P3.5.1.45
Remote Safety 2*
DigIN SlotA.3
1815
Defines the location of the remote safety.
P3.5.1.46
Remote Safety 3*
DigIN Slot0.2
1819
Defines the location of the remote safety.
P3.5.1.47
Remote Safety 4*
DigIN Slot0.2
1820
Defines the location of the remote safety.
P3.5.1.48
Remote Safety 5*
DigIN Slot0.2
1821
Defines the location of the remote safety.
P3.5.1.49
Remote Safety 6*
DigIN Slot0.2
1822
Defines the location of the remote safety.