Chapter 4 - Parameters and Menu Structure
Parameters (M3)
62 | 187
Siemens Industry, Inc.
Siemens BT300 HVAC Drive
DPD01809
Smart Infrastructure
2019-05-29
Structure
Parameter
Default
ID
Description
P3.5.1.50
Remote Safety 7*
DigIN Slot0.2
1823
Defines the location of the remote safety.
P3.5.1.51
Remote Safety 8*
DigIN Slot0.2
1824
Defines the location of the remote safety.
P3.5.1.52
Essential Services*
DigIN Slot0.1
1827
Defines the location of the essential service activation signal.
NOTE: Requires EssentServEnable (P3.18.5) to be enabled to
take effect.
P3.5.1.53
Overload
(Accessible when
Bypass (P3.17.4) =
Electronic or
Conventional
DigIN SlotA.5
1825
Defines the location of the bypass overload relay.
NOTE: Is it not recommended to change this value. The overload
relay is factory wired to digital input 5 on all Conventional and
Electronic Bypass options.
NOTE:
The status of the analog inputs can be monitored in the Multimonitor (M2.1)
view, or in the I/O and Hardware (M5) menu.
Structure
Parameter
Unit
Min
Max
Default
ID
Description
P3.5.2.1
AI1 Signal Sel
AnIN SlotA.1
377
Defines the location of the signal
to be used as analog input 1.
P3.5.2.2
AI1 Filter Time
s
0
300
1
378
Defines the time it takes to reach
63% of a step change in the
analog input signal defined by AI1
Signal Sel (P3.5.2.1).
When this parameter is given a
value > 0, the function that filters
out disturbances from the
incoming analog signal is
activated.
NOTE: Long filtering time makes
the regulation response slower.
P3.5.2.3
AI1 Signal Range
0-10V/
0-20 mA
2-10V/
4-20 mA
0-10V/
0-20 mA
379
Defines the signal range for the
analog input defined by AI1
Signal Sel (P3.5.2.1). Ranges are
as follows:
0 = 0 to 10 Vdc/0 to 20 mA
1 = 2 to 10 Vdc 4 to 20 mA
NOTE: This setting can be
bypassed by using AI1 Custom
Min (P3.5.2.4) and AI1 Custom
Max (P3.5.2.5).
P3.5.2.4
AI1 Custom Min
%
-160
160
0
380
Defines the custom minimum to
be used for bypassing the AI1
Signal Range (P3.5.2.3).