Operating Instructions

Chapter 4 - Parameters and Menu Structure
Parameters (M3)
63 | 187
Siemens Industry, Inc.
Siemens BT300 HVAC Drive
DPD01809
Smart Infrastructure
2019-05-29
Structure
Parameter
Unit
Min
Max
Default
ID
Description
P3.5.2.5
AI1 Custom Max
&
-160
160
100
381
Defines the custom maximum to
be used for bypassing the AI1
Signal Range (P3.5.2.3).
P3.5.2.6
AI1 Signal Inv
Normal
Inverted
Normal
387
Defines the operation of the
analog input 1 signal as follows:
Normal = 0V or 0 mA = 0%, 10V or
20 mA = 100%.
Inverted = 0V or 0 mA = 100%,
10V or 20 mA = 0%.
P3.5.2.7
AI2 Signal Sel
AnIN SlotA.2
388
Defines the location of the signal
to be used as analog input 2.
P3.5.2.8
AI2 Filter Time
s
0
300
1
389
Defines the time it takes to reach
63% of a step change in the
analog input signal defined by AI2
Signal Sel (P3.5.2.7).
P3.5.2.9
AI2 Signal Range
0-10V/0-
20mA
2-10V/4-
20mA
0-10V/0-
20mA
390
Defines the signal range for the
analog input defined by AI2
Signal Sel (P3.5.2.7). Ranges are
as follows:
0 = 0 to 10 Vdc/0 to 20 mA
1 = 2 to 10 Vdc / 4..20 mA
NOTE: This setting can be
bypassed by using AI2 Custom
Min (P3.5.2.10) and AI2 Custom
Max (P3.5.2.11).
P3.5.2.10
AI2 Cutom Min
%
-160
160
0
391
Defines the custom minimum to
be used for bypassing the AI2
Signal Range (P3.5.2.9).
P3.5.2.11
AI2 Custom Max
&
-160
160
100
392
Defines the custom maximum to
be used for bypassing the AI2
Signal Range (P3.5.2.9).
P3.5.2.12
AI2 Signal Inv
Normal
Inverted
Normal
398
Defines the operation of the
analog input 2 signal as follows:
Normal = 0V or 0 mA = 0%, 10V or
20 mA = 100%
Inverted = 0V or 0 mA = 100%,
10V or 20 mA = 0%
P3.5.2.13
AI3 Signal Sel
AnIN Slot0.1
141
Defines the location of the signal
to be used as analog input 3.
P3.5.2.14
AI3 Filter Time
s
0
300
1
142
Defines the time it takes to reach
63% of a step change in the
analog input signal defined by AI3
Signal Sel (P3.5.2.13).
P3.5.2.15
AI3 Signal Range
0-10V/0-
20mA
2-10V/4-
20mA
0-10V/
0-20 mA
143
Defines the signal P3.5.2.13).
Ranges are as follows:
0 = 0 to 10 Vdc/0 to 20 mA
1 = 2 to 10 Vdc/4 to 20 mA
NOTE: This setting can be
bypassed by using AI3 Custom
Min (P3.5.2.16) and AI3 Custom
Max (P3.5.2.17).
P3.5.2.16
AI3 Cutom Min
%
-160
160
0
144
Defines the custom minimum to
be used for bypassing the AI3
Signal Range (P3.5.2.15).