Operating Instructions

Chapter 4 - Parameters and Menu Structure
Parameters (M3)
64 | 187
Siemens Industry, Inc.
Siemens BT300 HVAC Drive
DPD01809
Smart Infrastructure
2019-05-29
Structure
Parameter
Unit
Min
Max
Default
ID
Description
P3.5.2.17
AI3 Custom Max
&
-160
160
100
145
Defines the custom maximum to
be used for bypassing the AI3
Signal Range (P3.5.2.15).
P3.5.2.18
AI3 Signal Inv
Normal
Inverted
Normal
151
Defines the operation of the
analog input 3 signal as follows:
Normal = 0V or 0 mA = 0%, 10V or
20 mA = 100%
Inverted = 0V or 0 mA = 100%,
10V or 20m A = 0%
P3.5.2.19
AI4 Signal Sel
AnIN Slot0.1
152
Defines the location of the signal
to be used as analog input 4.
P3.5.2.20
AI4 Filter Time
s
0
300
1
153
Defines the time it takes to reach
63% of a step change in the
analog input signal defined by AI4
Signal Sel (P3.5.2.19).
P3.5.2.21
AI4 Signal Range
0-10V/
0-20mA
2-10V/
4-20mA
0-10V/
0-20mA
154
Defines the signal range for the
analog input defined by AI4
Signal Sel (P3.5.2.19). Ranges are
as follows:
0 = 0 to 10 Vdc/0 to 20 mA
1 = 2 to 10 Vdc/4 to 20 mA
NOTE: This setting can be
bypassed by using AI4 Custom
Min (P3.5.2.22) and AI4 Custom
Max (P3.5.2.23).
P3.5.2.22
AI4 Cutom Min
%
-160
160
0
155
Defines the custom minimum to
be used for bypassing the AI4
Signal Range (P3.5.2.21).
P3.5.2.23
AI4 Custom Max
&
-160
160
100
156
Defines the custom maximum to
be used for bypassing the AI4
Signal Range (P3.5.2.21).
P3.5.2.24
AI4 Signal Inv
Normal
Inverted
Normal
162
Defines the operation of the
analog input 4 signal as follows:
Normal = 0V or 0 mA = 0%, 10V or
20 mA = 100%
Inverted = 0V or 0 mA = 100%,
10V or 20 mA = 0%
P3.5.2.25
AI5 Signal Sel
AnIN Slot0.1
188
Defines the location of the signal
to be used as analog input 5.
P3.5.2.26
AI5 Filter Time
s
0
300
1
189
Defines the time it takes to reach
63% of a step change in the
analog input signal defined by AI5
Signal Sel (P3.5.2.25).
P3.5.2.27
AI5 Signal Range
0-10V/
0-20 mA
2-10V/
4-20 mA
0-10V/
0-20 mA
190
Defines the signal range for the
analog input defined by AI5
Signal Sel (P3.5.2.25). Ranges are
as follows:
0 = 0 to 10 Vdc/0 to 20 mA
1 = 2 to 10 Vdc/4 to 20 mA
NOTE: This setting can be
bypassed by using AI5 Custom
Min (P3.5.2.28) and AI5 Custom
Max (P3.5.2.29).