Operating Instructions

Chapter 4 - Parameters and Menu Structure
Parameters (M3)
65 | 187
Siemens Industry, Inc.
Siemens BT300 HVAC Drive
DPD01809
Smart Infrastructure
2019-05-29
Structure
Parameter
Unit
Min
Max
Default
ID
Description
P3.5.2.28
AI5 Cutom Min
%
-160
160
0
191
Defines the custom minimum to
be used for bypassing the AI5
Signal Range (P3.5.2.27).
P3.5.2.29
AI5 Custom Max
&
-160
160
100
192
Defines the custom maximum to
be used for bypassing the AI5
Signal Range (P3.5.2.27).
P3.5.2.30
AI5 Signal Inv
Normal
Inverted
Normal
198
Defines the operation of the
analog input 5 signal as follows:
Normal = 0Vor 0 mA = 0%, 10V or
20 mA = 100%
Inverted = 0V or 0 mA = 100%,
10V or 20 mA = 0%
P3.5.2.31
AI6 Signal Sel
AnIN Slot0.1
199
Defines the location of the signal
to be used as analog input 6.
P3.5.2.32
AI6 Filter Time
s
0
300
1
200
Defines the time it takes to reach
63% of a step change in the
analog input signal defined by AI6
Signal Sel (P3.5.2.31).
P3.5.2.33
AI6 Signal Range
0-10V/
0-20mA
2-10V/
4-20 mA
0-10V/
0-20 mA
201
Defines the signal range for the
analog input defined by AI6
Signal Sel (P3.5.2.31). Ranges are
as follows:
0 = 0 to 10 Vdc/0 to 20 mA
1 = 2 to 10 Vdc/4 to 20 mA
NOTE: This setting can be
bypassed by using AI6 Custom
Min (P3.5.2.34) and AI6 Custom
Max (P3.5.2.35).
P3.5.2.34
AI6 Cutom Min
%
-160
160
0
203
Defines the custom minimum to
be used for bypassing the AI6
Signal Range (P3.5.2.33).
P3.5.2.35
AI6 Custom Max
&
-160
160
100
204
Defines the custom maximum to
be used for bypassing the AI6
Signal Range (P3.5.2.33).
P3.5.2.36
AI6 Signal Inv
Normal
Inverted
Normal
209
Defines the operation of the
analog input 6 signal as follows:
Normal = 0V or 0 mA = 0%, 10V or
20 mA = 100%
Inverted = 0V or 0 mA = 100%,
10V or 20 mA = 0%
NOTE:
The status of the Digital/Relay Outputs can be monitored in the Multimonitor
(M2.1) view, or in the I/O and Hardware (M5) menu.