Operating Instructions

Chapter 4 - Parameters and Menu Structure
Parameters (M3)
66 | 187
Siemens Industry, Inc.
Siemens BT300 HVAC Drive
DPD01809
Smart Infrastructure
2019-05-29
Structure
Parameter
Unit
Min
Max
Default
ID
Description
P3.5.3.2.1
RO1 Function
None
Remote
Start
Run
11001
See
Basic RO Functions Table
.
P3.5.3.2.2
RO1 ON Delay
s
0
320
0
11002
Defines the amount of time that
will pass before the relay output
will energize (ON) after trigger of
the RO1 Function (P3.5.3.2.1).
P3.5.3.2.3
RO1 OFF Delay
s
0
320
0
11003
Defines the amount of time that
will pass before the relay output
will de-energize (OFF) after
trigger of the RO1 Function
(P3.5.3.2.1).
P3.5.3.2.4
RO2 Function
None
Remote
Start
General
Fault
11004
See
Basic RO Functions Table
.
P3.5.3.2.5
RO2 ON Delay
s
0
320
0
11005
Defines the amount of time that
will pass before the relay output
will energize (ON) after trigger of
the RO2 Function (P3.5.3.2.4).
P3.5.3.2.6
RO2 OFF Delay
s
0
320
0
11006
Defines the amount of time that
will pass before the relay output
will de-energize (OFF) after
trigger of the RO2 Function
(P3.5.3.2.4).
P3.5.3.2.7
RO3 Function
None
Remote
Start
Ready
11007
See
Basic RO Functions Table
.
Selection
Selection name
Description
0
Not used
1
Ready
The variable frequency drive is ready to operate.
2
Run
The variable frequency drive operates (motor is running).
3
General fault
A fault trip has occurred.
4
General fault inverted
A fault trip has
not
occurred.
5
General alarm
6
Reversed
The reverse command has been selected.
7
At speed
The output frequency has reached the set reference.
8
Motor regulator activated
One of the limit regulators (for example, current limit or torque limit)
is activated.
9
Preset frequency active
The preset frequency has been selected with digital input.
10
Keypad control active
Keypad control mode selected.
11
I/O control B active
I/O control place B selected.
12
Limit supervision 1