Operating Instructions

Chapter 4 - Parameters and Menu Structure
Parameters (M3)
67 | 187
Siemens Industry, Inc.
Siemens BT300 HVAC Drive
DPD01809
Smart Infrastructure
2019-05-29
Selection
Selection name
Description
13
Limit supervision 2
Activates if the signal value falls below or exceeds the set supervision
limit (P3.8.3 or P3.8.7) depending on the selected function.
14
Start command active
Start command is active.
15
Reserved
16
Fire mode ON
17
RTC timer 1 control
Time channel 1 is used.
18
RTC timer 2 control
Time channel 2 is used.
19
RTC timer 3 control
Time channel 3 is used.
20
FB Control WordB.13
21
FB Control WordB.14
22
FB Control WordB.15
23
PID1 in Sleep mode
24
Reserved
25
PID1 supervision limits
PID1 feedback value is beyond supervision limits.
26
PID2 supervision limits
PID2 feedback value is beyond supervision limits.
27
Motor 1 control
Contactor control for
Multi-pump
function.
28
Motor 2 control
Contactor control for
Multi-pump
function.
29
Motor 3 control
Contactor control for
Multi-pump
function.
30
Motor 4 control
Contactor control for
Multi-pump
function.
31
Reserved
(Always open.)
32
Reserved
(Always open.)
33
Reserved
(Always open.)
34
Maintenance warning
35
Maintenance fault
36
Thermistor fault
37
Motor switch
38
Bypass active
Selects relay output for the Bypass active signal. This signal is on
when the drive is in Bypass mode.
39
Bypass running
Selects relay output terminal for Bypass contactor control.
40
Drive active
Selects relay output for the Drive active signal. This signal is on when
the drive is in Drive mode.
41
Drive output contactor
Controls the Drives Output contactor.
42
Overload Fault
Selects relay output for the Overload fault signal. This signal is on
when the Overload fault is active.
43
Essential Services active
Selects relay output for the Essential services signal.
44
Auto Bypass active
Selects relay output for the Auto Bypass active signal