Operating Instructions

Chapter 4 - Parameters and Menu Structure
Parameters (M3)
69 | 187
Siemens Industry, Inc.
Siemens BT300 HVAC Drive
DPD01809
Smart Infrastructure
2019-05-29
Structure
Parameter
Unit
Min
Max
Default
ID
Description
P3.5.3.5.1
RO1 Function
None
Remote Start
None
14001
See
Basic RO Functions Table
.
P3.5.3.5.2
RO2 Function
None
Remote Start
None
14002
P3.5.3.5.3
RO3 Function
None
Remote Start
None
14003
P3.5.3.5.4
RO4 Function
None
Remote Start
None
14004
P3.5.3.5.5
RO5 Function
None
Remote Start
None
14005
P3.5.3.5.6
RO6 Function
None
Remote Start
None
14006
NOTE:
The status of the Analog Outputs can be monitored in the Multimonitor (P2.1)
view, or in the I/O and Hardware (M5) menu.
Structure
Parameter
Unit
Min
Max
Default
ID
Description
P3.5.4.1.1
AO1 Function
0% Test
ProcessDataIn8
Output
Frequency
10050
See
AO Functions Table
.
P3.5.4.1.2
AO1 Filter Time
s
0
300
1
10051
Filter time of analog output signal
0 = No filtering
P3.5.4.1.3
AO1 Min Signal
0 Vdc/0 mA
2 Vdc/4 mA
0 Vdc/0 mA
10052
Settings:
0 = 0 Vdc/0 mA
1 = 2 Vdc/4 mA
P3.5.4.1.4
AO1 MinScale
Varies
Varies
Varies
10053
Min Scale in process unit.
P3.5.4.1.5
AO1 MaxScale
Varies
Varies
Varies
10054
Max Scale in process unit
Settings
Description
0
0% Test
AO is not used. 0 output.
1
100% Test
AO is max. 10 Vdc or 20 mA output.
2
Output Frequency
Track the Output Frequency based on 0 to Max Frequency (P3.3.2).
3
Freq Reference
Track the Frequency Reference base on 0 to Max Frequency (P3.3.2).
4
Motor Speed
Track the Motor Speed based on 0 to Motor Nom Speed (P3.1.1.3).
5
Output Current
Track the Output Current based on 0 to Motor Nom Currnt (P3.1.1.4).
6
Motor Torque
Track the Motor Torque based on 0 to TnMotor.