Operating Instructions

Chapter 4 - Parameters and Menu Structure
Parameters (M3)
70 | 187
Siemens Industry, Inc.
Siemens BT300 HVAC Drive
DPD01809
Smart Infrastructure
2019-05-29
Settings
Description
7
Motor Power
Track the Motor Power based on 0 to PnMotor.
8
Motor Voltage
Track the Motor Voltage based on 0 to VnMotor.
9
DC Link Voltage
Track the DC Link Voltage based on 0 - 1000 Vdc.
10
PID 1 Output
Track the PID1 Output based on 0 - 100%
11
PID 2 Output
Track the PID2 Output based on 0 - 100%.
12
Process Data In 1
Track the Process Data In 1 where 5000 = 50.00%.
13
Process Data In 2
Track the Process Data In 2 where 5000 = 50.00%.
14
Process Data In 3
Track the Process Data In 3 where 5000 = 50.00%.
15
Process Data In 4
Track the Process Data In 4 where 5000 = 50.00%.
16
Process Data In 5
Track the Process Data In 5 where 5000 = 50.00%.
17
Process Data In 6
Track the Process Data In 6 where 5000 = 50.00%.
18
Process Data In 7
Track the Process Data In 7 where 5000 = 50.00%.
19
Process Data In 8
Track the Process Data In 8 where 5000 = 50.00%.
Structure
Parameter
Unit
Min
Max
Default
ID
Description
P3.5.4.3.1
AO1 Function
0% Test
ProcessDataIn8
0% Test
12050
See
AO Functions Table.
P3.5.4.3.2
AO1 Filter Time
s
0
300
1
12051
Filter time of analog output signal
0 = No filtering
P3.5.4.3.3
AO1 Min Signal
0 Vdc/0 mA
2 Vdc/4 mA
0 Vdc/0 mA
12052
Settings:
0 = 0 Vdc/0 mA
1 = 2 Vdc/4 mA
P3.5.4.3.4
AO1 MinScale
Varies
Varies
Varies
12053
Min Scale in process unit.
P3.5.4.3.5
AO1 MaxScale
Varies
Varies
Varies
12054
Max Scale in process unit
P3.5.4.3.6
AO2 Function
0% Test
ProcessDataIn8
0% Test
12055
See
AO Functions Table.
P3.5.4.3.7
AO2 Filter Time
s
0
300
1
12056
Filter time of analog output signal
0 = No filtering
P3.5.4.3.8
AO2 Min Signal
0 Vdc/0 mA
2 Vdc/4 mA
0 Vdc/0 mA
12057
Settings:
0 = 0 Vdc/0 mA
1 = 2 Vdc/4 mA
P3.5.4.3.9
AO2 MinScale
Varies
Varies
Varies
12058
Min Scale in process unit.
P3.5.4.3.10
AO2 MaxScale
Varies
Varies
Varies
12059
Max Scale in process unit