NOTE:
The drive will still ramp through these speeds, but will not control within this
range. The speed at which the drive ramps through this range can be changed by
the Ramp Time Factor (P3.7.7) to make it faster.
For example. If Acceleration Time 1 (P3.4.2) is set to a value of 120, Minimum
Frequency (P3.3.1) is set to a value of 0, and Maximum Frequency (P3.3.2) is
set to a value of 60; then it takes 2 seconds to speed up 1 hertz. If Ramp Time
Factor (P3.7.7) is set to a value of 2, then it takes 1 second to speed up 1 hertz
when within the range as defined by Prohibited Frequency Range 1 Low Limit
(P3.7.1) and Prohibited Frequency Range 1 High Limit (P3.7.2)
Structure
Parameter
Unit
Min
Max
Default
ID
Description
P3.8.1
Superv1 Item
Output
Frequency
Analog Input 2
Output Frequency
1431
Defines the drive data to supervise for
Superv1 Mode (P3.8.2) in accordance
with the Superv1 Limit (P3.8.3) with
deadband defined with Superv1 Hyst
(P3.8.4)
0 = Output Frequency
1 = Frequency Reference
2 = Motor Current
3 = Motor Torque
4 = Motor Power
5 = DC-Link Voltage
6 = Analog Input 1
7 = Analog Input 2
NOTE:
A relay output can be triggered
in accordance with this supervised
item. Set Relay Output Function to a
value of Superv1 Lmt.
P3.8.2
Superv1 Mode
Not Used
High Limit
Not Used
1432
Defines the type of supervision of the
Superv1 Item (P3.8.1) in accordance
with the Superv1 Limit (P3.8.3) with
deadband defined with Superv1 Hyst
(P3.8.4)
0 = Not used
1 = Low Limit Supervision
2 = High Limit Supervision
P3.8.3
Superv1 Limit
Varies
-200
200
25
1433
Defines the limit that Superv1 Item
(P3.8.1) is compared to, which
determines if Superv1 Mode (P3.8.2)
has occurred. Unit of measure
displays automatically.
P3.8.4
Superv1 Hyst
Varies
-200
200
5
1434
Defines the deadband of Superv1
Item (P3.8.1).