Operating Instructions

Chapter 4 - Parameters and Menu Structure
Parameters (M3)
80 | 187
Siemens Industry, Inc.
Siemens BT300 HVAC Drive
DPD01809
Smart Infrastructure
2019-05-29
Structure
Parameter
Unit
Min
Max
Default
ID
Description
P3.9.22
PID1 Supervision
No Action
Fault, Coast
Fault
749
Defines the response to a PID1 fault.
Response settings are as follows:
0 = No Action
1 = Alarm
2 = Fault
(stop according to stop mode)
3 = Fault
(stop by coasting)
P3.9.23
PID2 Supervision
No Action
Fault, Coast
Fault
757
Defines the response to a PID2 fault.
Response settings are as follows:
0 = No Action
1 = Alarm
2 = Fault
(stop according to stop mode)
3 = Fault
(stop by coasting)
P3.9.25
TempFault Signal
Not Used
TempInput1
-3
Not Used
739
Defines the source signal to monitor for
TempAlarm Limit (P3.9.26) and
TempFault Limit (P3.9.27) triggering.
Settings:
0 = Not used
1 = Temperature Input 1
2 = Temperature Input 2
3 = Temperature Input 3
4 = Temperature Inputs 1 & 2
5 = Temperature Inputs 2 & 3
6 = Temperature Inputs 1 & 3
P3.9.26
TempAlarm Limit
-30
200
130
741
Defines the temperature that TempFault
Signal (P3.9.25) must reach for triggering
an alarm.
P3.9.27
TempFault Limit
-30
200
155
742
Defines the temperature that TempFault
Signal (P3.9.25) must reach for triggering
a fault.
P3.9.28
TempFault Response
No Action
Fault, Coast
Fault
740
Defines the response action when
TempFault Signal (P3.9.25) has past
TempFault Limit (P3.9.27). Response
settings are as follows:
0 = No Action
1 = Alarm
2 = Fault
(stop according to stop mode)
3 = Fault
(stop by coasting)
P3.9.29
Run Interlock Flt
No Action
Fault, Coast
No Action
14061
Defines the response action to a Run
Interlock Fault. This requires Mot.
Interlock Start (P3.2.11) to be enabled,
Run Interlock 1 (P3.5.1.12) or Run
Interlock 2 (P3.5.1.13) to be defined to a
digital input and a value defined for Run
Interlock Proof (P3.2.13) other than 0.