Operating Instructions

Chapter 4 - Parameters and Menu Structure
Parameters (M3)
88 | 187
Siemens Industry, Inc.
Siemens BT300 HVAC Drive
DPD01809
Smart Infrastructure
2019-05-29
Structure
Parameter
Unit
Min
Max
Default
ID
Description
P3.11.1.1
ON Time
hh:mm:ss
0:00:00
23:59:59
1464
ON Time
Defines the time ON is issued to
the time the channel defined in
AssignToChannel (P3.11.1.5)
on the day of week defined in
From Day (P3.11.1.3) to and
including day defined in To Day
(P3.11.1.4).
P3.11.1.2
OFF Time
hh:mm:ss
0:00:00
23:59:59
1465
OFF Time
Defines the time OFF is issued
to the time channel defined in
AssignToChannel (P3.11.1.5)
on the day of week defined in
From Day (P3.11.1.3) to and
including day defined in To Day
(P3.11.1.4).
P3.11.1.3
From Day
Sunday
Saturday
1466
From Day
Defines the beginning day of the
week the ON Time (P3.11.1.1)
and OFF Time (P3.11.1.2) are
issued to the unit.
0 = Sunday
1 = Monday
2 = Tuesday
3 = Wednesday
4 = Thursday
5 = Friday
6 = Saturday
P3.11.1.4
To Day
Sunday
Saturday
1467
To Day
Defines the ending day of the
week the ON Time (P3.11.1.1)
and OFF Time (P3.11.1.2) are
issued to the unit.
0 = Sunday
1 = Monday
2 = Tuesday
3 = Wednesday
4 = Thursday
5 = Friday
6 = Saturday
P3.11.1.5
AssignToChannel
Not Used
Time
Channel 3
1468
AssignToCha
nnel
Defines the affected time
channel of the ON Time
(P3.11.1.1) and OFF Time
(P3.11.1.2)
0 = Not used
1 = Time Channel 1
2 = Time Channel 2
3 = Time Channel 3