Operating Instructions

Chapter 4 - Parameters and Menu Structure
Parameters (M3)
94 | 187
Siemens Industry, Inc.
Siemens BT300 HVAC Drive
DPD01809
Smart Infrastructure
2019-05-29
Structure
Parameter
Unit
Min
Max
Default
ID
Description
P3.12.2.4
SP 1 Source
Not Used
Test
Sequence
Keypad
SP1
332
See Table
Setpoint Source
.
AIs and ProcessDataIn's are
handled as percent and scaled
according to Setpoint Min and
Setpoint Max.
NOTE: ProcessDataIn uses two
decimals.
P3.12.2.5
SP 1 Minimum
%
-200
200
0
1069
Minimum value of Setpoint at
Analog Signal Minimum.
P3.12.2.6
SP 1 Maximum
%
-200
200
100
1070
Maximum value of Setpoint at
Analog Signal Maximum.
P3.12.2.7
SP 1 Sleep Freq
Hz
0
320
0
1016
Define the frequency at which
Sleep Mode activates.
P3.12.2.8
SP 1 Sleep Delay
s
0
3000
0
1017
Minimum amount of time the
frequency has to remain below
Sleep Level before the drive is
stopped.
P3.12.2.9
SP 1 WakeUpLevel
Varies
0
1018
Defines the level for the PID
feedback value wake-up
supervision.
P3.12.2.10
SP 1 Boost
x
-2
2
1
1071
Setpoint can be boosted with a
digital input.
P3.12.2.11
SP 2 Source
Not Used
Test
Sequence
Keypad
SP2
431
See description for
SP 1 Source
(P3.12.2.4)
P3.12.2.12
SP 2 Minimum
%
-200
200
0
1073
Minimum value of Setpoint at
Analog Signal Minimum.
P3.12.2.13
SP 2 Maximum
%
-200
200
100
1074
Maximum value of Setpoint at
Analog Signal Maximum.
P3.12.2.14
SP 2 Sleep Freq
Hz
0
320
0
1075
Define the frequency at which
Sleep Mode activates.
P3.12.2.15
SP 2 Sleep Delay
s
0
3000
0
1076
Minimum amount of time the
frequency has to remain below
Sleep Level before the drive is
stopped.
P3.12.2.16
SP 2 WakeUpLevel
Varies
0
1077
Defines the level for the PID
feedback value wake-up
supervision.
P3.12.2.17
SP 2 Boost
x
-2
2
1
1078
Setpoint can be boosted with a
digital input.
Settings
Description
0
Not Used
Setpoint is not used.
1
Keypad Setpoint 1
Use keypad setpoint 1.
2
Keypad Setpoint 2
Use keypad setpoint 2.
3
AI1
Use analog input 1.
4
AI2
Use analog input 2.