Operating Instructions

Chapter 4 - Parameters and Menu Structure
Parameters (M3)
96 | 187
Siemens Industry, Inc.
Siemens BT300 HVAC Drive
DPD01809
Smart Infrastructure
2019-05-29
Structure
Parameter
Unit
Min
Max
Default
ID
Description
P3.12.3.5
FB 1 Maximum
%
-200
200
100
337
Maximum value at Analog Signal
Maximum.
P3.12.3.6
FB 2 Source
Not Used
ProcessData
In8
Not Used
335
See
FB 1 Source
(P3.12.3.3)
.
P3.12.3.7
FB 2 Minimum
%
-200
200
0
338
Minimum value at Analog Signal
Minimum.
P3.12.3.8
FB 2 Maximum
%
-200
200
100
339
Maximum value at Analog Signal
Maximum.
Settings
Description
0
Not Used
Setpoint is not used.
1
AI1
Use analog input 1.
2
AI2
Use analog input 2.
3
AI3
Use analog input 3.
4
AI4
Use analog input 4.
5
AI5
Use analog input 5.
6
AI6
Use analog input 6.
7
ProcessDataIn1
Use ProcessDataIn1.
8
ProcessDataIn2
Use ProcessDataIn2.
9
ProcessDataIn3
Use ProcessDataIn3.
10
ProcessDataIn4
Use ProcessDataIn4.
11
ProcessDataIn5
Use ProcessDataIn5.
12
ProcessDataIn6
Use ProcessDataIn6.
13
ProcessDataIn7
Use ProcessDataIn7.
14
ProcessDataIn8
Use ProcessDataIn8.