Specifications
Table 1. Drive Specifications.
Specification
Description
Input Voltages and Power Ranges
(3-phase)
208 to 240 Vac (-10% to +10%):
1 hp to 125 hp (0.75 kW to 90 kW)
380 to 500 Vac (-10% to +10%):
1.5 hp to 250 hp (1.1 kW to 160 kW)
525 to 600 Vac (-10% to+10%):
3 hp to 200 hp (2.2 kW to 132 kW)
Input Frequency
45 to 66 Hz (50 to 60 Hz; -5% to +10%)
Output Voltage
0 to Input voltage
Output Frequency
0 to 320 Hz
Output Frequency Resolution
0.01 Hz
Efficiency
>97.5%
Overload Capacity
1.1 * nominal rated output current 110% for 1 minute/10 minutes
PWM (switching) frequency
FS4 to FS6 - 1.5 to 10 kHz
Default FS4: 6 kHz; FS5: 4 kHz; FS6 = 4 kHz
FS7 to FS9 - 1.5 to 6 kHz
Default FS7: 4 kHz; FS8: 3 kHz; FS9: 2kHz
Adjustable in .1 kHz increments
Automatic switching frequency derating in case of overheating
Short circuit withstand rating
100,000 AIC
Frequency Reference
Analog Input
Keypad
Resolution 0.01 to 0.1% (10 bit), accuracy ±1%
Resolution 0.01 Hz
Field weakening point
8 to 320 Hz
Acceleration time
0.1 to 3000.0 seconds
Deceleration time
0.1 to 3000.0 seconds
Ambient Operating Temperature
14°F (-10°C) (no frost) to 104°F (40°C)
up to 122°F (50°C) with derating
Storage Temperature
-40°F (-40°C) (no frost) to 158°F (70°C)
Relative Humidity
0 to 95% rh, non-condensing, non-corrosive
Air quality:
Chemical vapors
Mechanical particles
IEC 60068-2-60 (H
2
S [hydrogen sulfide] and SO
2
[sulfur dioxide]).
IEC 60721-3-3, unit in operation, class 3C2
IEC 60721-3-3, unit in operation, class 3S3.
Altitude
100% load capacity (no-derating) up to 3,280 ft (1,000 m)
-1% derating for each 328 ft (100 m) above 3,280 ft (1,000 m)
Maximum altitude:
208 to 240 Vac: 13,123 ft (4,000 m)
380 to 500 Vac: 13,123 ft (4,000 m)
525 to 600 Vac: 6,562 ft (2,000 m)
Voltage for relay outputs:
240 Vac: ≤ 9,842 ft (3,000 m)
120 Vac: ≤ 13,123 ft (4,000 m)
Corner-grounding (380-500 Vac systems only):
≤ 6,562 ft (2,000 m)
Fixed frequencies
7 programmable
Skip (prohibited) frequency band
3 programmable
Vibration
EN61800-5-1
EN60068-2-6
Seismic
2012 International Building Code (IBC)
Shock
EN61800-5-1
EN60068-2-27
Enclosure Class
UL Type 1/IP 21 standard in entire HP/kW range.
UL Type 12/IP 54 options