Data Sheet for Product

Submittal Sheet
Document No. 154-129
February 19, 2018
BT300 HVAC Drives Electronic
Bypass (E-Bypass) Options
Siemens Industry, Inc.
Description
The BT300 Electronic Bypass (E-Bypass) Options are
companion packages for the family of BT300 Variable
Frequency Drives (VFDs).
For information on the family of BT300 VFDs, see the BT300
HVAC Drives Submittal Sheet (154-126), and BT300 HVAC
Drives Technical Specification Sheet (149-711).
BT300 E-Bypass Features
Bypass Start-up Wizard
Diagnostic board with test points
Control logic short circuit protection
100,000 AIC short circuit rating
Auto Bypass
Damper Interlock
Essential Service Mode
Remote Bypass
Electronic Override
View/Monitor bypass parameters
Multiple Safeties
Monitor and display which safety interlock is open
Control external devices via serial communication
Pass through I/O capabilities command up to 8 output
points
View status of I/O points
Supports APOGEE P1, BACnet and Modbus protocols
in bypass
IBC 2012 Seismic Certified
OSHPD Certified
Compact design
E-Bypass Power Features
2-Contactor: Output and Bypass
Overload protection in bypass mode
Electrically interlocked
Drive Isolation
Drive Service Switch allows the drive to be disconnected
from power during troubleshooting without disrupting bypass
operation.
Input Device
Disconnect with fuses.
(Optional) Circuit breaker.
All doors are interlocked and can be padlocked
5% Input Impedance
Internal reactors lower harmonics that the drive
produces.
BT300 E-Bypass requires no additional input reactors
E-Bypass Control Features
Auto Bypass
Relay logic allows the user to send the motor to bypass
mode based on the drive’s programmable fault list.
Customer defines the events which will transfer to
bypass.
The drive’s programmable relay can be set up for
applications that run full speed for an extended period
of time.
Damper Interlock
Generally used for safety tie-ins; the motor will not
operate the drive or bypass when open.
Enables a circuit signaling the system is ready for
bypass.
Essential Service Mode
Also used for smoke purge; the motor goes to bypass
regardless of the selected mode.
No call to stop will have an effect, including open
safety or stop commands.
Only turning the power off or opening this contact will
stop the motor.
Remote Bypass
Customer-supplied start/stop controls when running in
bypass.
Electronic Override
Full bypass control, even if the control module
(intelligence) fails. As long as power is supplied to the
bypass, you have full bypass capability.
Maintains all system safeties in bypass.