Installation Instructions Document No. DPD01375 August 24, 2018 BT300 Variable Frequency Drive Bypass Product Description Warning/Caution Notations CAUTION/ATTENTION The Siemens BT300 Bypasses are companion packages for the family of BT300 HVAC Variable Speed Drives. Equipment damage or loss of data may occur if you do not follow a procedure as specified. Product Numbers Risque de dégâts matériels ou de perte de données, en cas de non-respect des procédures à suivre.
Document No. DPD01375 Installation Instructions August 24, 2018 Table 1. Minimum Clearance around Bypass in Inches (cm). Frame Size A B C FS4 6.75 (17.15) 6.75 (17.15) 3.93 (9.98) 0 FS5 6.75 (17.15) 6.75 (17.15) 4.72 (11.99) 0 FS6 8.75 (22.23) 8.75 (22.23) 6.29 (15.98) 0 FS7 14.13 (35.89) 14.13 (35.89) 9.84 (24.99) 0 FS8 12 (30.48) 18 (45.72) 24 (60.96) 12 (30.48) FS9 18 (45.72) 24 (60.96) 36 (91.
Document No. DPD01375 Installation Instructions August 24, 2018 • Table 2 also applies to the minimum separation between the motor cables and signal cables of other systems. Table 2. Minimum Cable Separation. Bypass Frame Sizes, Current Ratings, and Power Ranges Table 5. BT300 Bypass Frame Sizes and Power Ranges per NEC Motor Tables. Shielded cable [ft (m)] Distance Between Cables [ft (m)] < 164 (50) 1.0 (0.3) HP kW < 656 (200) 3.28 (1.0) 1 1.5 2 3 5 7.
Document No. DPD01375 Installation Instructions August 24, 2018 NOTE: The overloads are dialed in by the factory, based on the NEC FLA rating tables, and assume a trip (activation) level at 125%. If the 125% is acceptable for your installation, dial in the overload to match the connected motor's FLA rating. If a different percentage is desired, a multiplier must be used to determine the proper setting. This is a twostep process: First, determine the multiplier.
Document No. DPD01375 Installation Instructions August 24, 2018 Mounting and Dimensions Figure 2. Dimensions in Inches (cm) for UL (NEMA) Type 1 FS4 through FS7. Siemens Industry, Inc.
Document No. DPD01375 Installation Instructions August 24, 2018 Figure 3. Dimensions in Inches (cm) for UL (NEMA) Type 1 FS8. Figure 4. Dimensions in Inches (cm) for UL (NEMA) Type 1 FS9. Page 6 of 36 Siemens Industry, Inc.
Document No. DPD01375 Installation Instructions August 24, 2018 Figure 5. Conduit Locations for UL Type 1 FS4 through FS7 Bypasses. Figure 6. Conduit Locations for UL Type 1 FS8 Bypass. NOTES: 1. Knockout locations have not been provided for the Input and/or Output power connections; connections are completed by the customer. 2. The Input and Output power connection cannot be in the same conduit. 3. The Input and Output connections must be at least 6 inches away from the control wiring. 4.
Document No. DPD01375 Installation Instructions August 24, 2018 Figure 7. Conduit Locations for UL Type 1 FS9 Bypasses. NOTES: 1. Knockout locations have not been provided for the Input and/or Output power connections; connections are completed by the customer. 2. The Input and Output power connection cannot be in the same conduit. 3. The Input and Output connections must be at least 6 inches away from the control wiring. 4.
Document No. DPD01375 Installation Instructions August 24, 2018 Wiring Wire Sizes and Tightening Torques Table 6. Wire Sizes and Tightening Torques for Bypass with 208V to 240V Drive. Torque lb-in (Nm) Disconnect Switch Torque Wire lb-in Size* (Nm) 20-60 (2.3-6.8) 20-60 (2.3-6.8) 20-60 (2.3-6.8) 20-60 (2.3-6.8) 14-4 Cu 14-4 Cu 14-4 Cu 14-4 Cu 20-60 (2.3-6.8) Circuit Breaker Part Number HP kW BT_-001X2-… 1 0.75 BT_-00152-… 1.5 1.1 Frame Size Amps Wire Size* 4.8 10-1/0 Cu 6.
Document No. DPD01375 Installation Instructions August 24, 2018 Table 7. Wire Sizes and Tightening Torques for Bypass with 380V to 500V Drive. Circuit Breaker Part Number HP kW Frame Size Amps Disconnect Switch Overload Ground Lug Wire Size* Torque lb-in (Nm) Wire Size* Torque lb-in (Nm) Wire Size* Torque lb-in (Nm) Range Wire Size* Torque lb-in (Nm) BT_-00154-... 1.5 1.1 3.4 10-1/0 Cu 20-60 (2.3-6.8) 14-4 Cu 35 (3.95) 20-12 Cu 7-10.6 (0.8-1.2) 2.2-3.2 14-6 Cu 35 (3.
Document No. DPD01375 Installation Instructions August 24, 2018 Wiring Connections 1. Route shielded twisted pair (recommended wire type) cable, 24-gauge minimum control wiring in conduit, through knockout, and into housing. 6. Connect motor wiring to motor overload and ground lug. See Table 2 and for wire sizes and tightening torques. 7. Route input power wiring in conduit, through • For Electronic Bypass, see Figure 8 through Figure 15. • For Conventional Bypass, see Figure 22 through Figure 29.
Document No. DPD01375 Installation Instructions August 24, 2018 Electronic Bypass Diagrams Figure 8. FS4 E-Bypass with Circuit Breaker Components. Figure 9. FS4 E-Bypass with Disconnect with Fuses Components. Page 12 of 36 Siemens Industry, Inc.
Document No. DPD01375 Installation Instructions August 24, 2018 Figure 10. FS5 E-Bypass with Circuit Breaker Components. Figure 11. FS5 E-Bypass with Disconnect with Fuses Components. Siemens Industry, Inc.
Document No. DPD01375 Installation Instructions August 24, 2018 Figure 12. FS6 E-Bypass with Circuit Breaker Components. Figure 13. FS6 E-Bypass with Disconnect with Fuses Components. Page 14 of 36 Siemens Industry, Inc.
Document No. DPD01375 Installation Instructions August 24, 2018 Figure 14. FS7 E-Bypass with Circuit Breaker Components. Figure 15. FS7 E-Bypass with Disconnect with Fuses Components. Siemens Industry, Inc.
Document No. DPD01375 Installation Instructions August 24, 2018 Figure 16. FS8-E-Bypass with Circuit Breaker Components. Figure 17. FS8 E-Bypass with Disconnect with Fuses Components. Page 16 of 36 Siemens Industry, Inc.
Document No. DPD01375 Installation Instructions August 24, 2018 Figure 18. FS9 E-Bypass with Circuit Breaker Components. Figure 19. FS9 E-Bypass with Disconnect with Fuses Components. Siemens Industry, Inc.
Document No. DPD01375 Installation Instructions August 24, 2018 Figure 20. Electronic Bypass Drive Terminations. Page 18 of 36 Siemens Industry, Inc.
Document No. DPD01375 Installation Instructions August 24, 2018 NOTES: 1. Branch circuit protection to be provided by installer, per any National or local code requirements, as applicable. 2. Control and communication wiring should be 300V UL minimum. 3. Communication wiring should be run with maximum separation possible from all other wiring. 4. Essential service mode operates the motor full speed (bypass) with no protection for the motor or system. 5.
Document No. DPD01375 Installation Instructions August 24, 2018 Conventional Bypass Diagrams Figure 22. FS4 C-Bypass with Circuit Breaker Components. Figure 23. FS4 C-Bypass with Disconnect with Fuses Components. Page 20 of 36 Siemens Industry, Inc.
Document No. DPD01375 Installation Instructions August 24, 2018 Figure 24. FS5 C-Bypass with Circuit Breaker Components. Figure 25. FS5 C-Bypass with Disconnect with Fuses Components. Siemens Industry, Inc.
Document No. DPD01375 Installation Instructions August 24, 2018 Figure 26. FS6 C-Bypass with Circuit Breaker Components. Figure 27. FS6 C-Bypass with Disconnect with Fuses Components. Page 22 of 36 Siemens Industry, Inc.
Document No. DPD01375 Installation Instructions August 24, 2018 Figure 28. FS7 C-Bypass with Circuit Breaker Components. Figure 29. FS7 C-Bypass with Disconnect with Fuses Components. Siemens Industry, Inc.
Document No. DPD01375 Installation Instructions August 24, 2018 Figure 30. FS8 C-Bypass with Circuit Breaker Components. Figure 31. FS8 C-Bypass with Disconnect with Fuses Components. Page 24 of 36 Siemens Industry, Inc.
Document No. DPD01375 Installation Instructions August 24, 2018 Figure 32. FS9 C-Bypass with Circuit Breaker Components. Figure 33. FS9 C-Bypass with Disconnect with Fuses Components. Siemens Industry, Inc.
Document No. DPD01375 Installation Instructions August 24, 2018 Figure 34. Conventional Bypass Drive Terminations. Page 26 of 36 Siemens Industry, Inc.
Document No. DPD01375 Installation Instructions August 24, 2018 NOTES: 1. Branch circuit protection to be provided by installer, per any National or local code requirements, as applicable. 2. Control and communication wiring should be 300V UL minimum. 3. Communication wiring should be run with maximum separation possible from all other wiring. 4. Essential service mode operates the motor full speed (bypass) with no protection for the motor or system. 5.
Document No. DPD01375 Installation Instructions August 24, 2018 Bypass Power Circuit Wiring Diagrams NOTES: 1. Incoming power phase rotation should be L1, L2, L3 to match inverter forward direction phase rotation U, V, W. Connection as shown should produce clockwise direction when viewing the motor from the shaft end. Always test motor direction in both drive and bypass modes before coupling the motor to the load. 2.
Document No. DPD01375 Installation Instructions August 24, 2018 NOTES: 1. Incoming power phase rotation should be L1, L2, L3 to match inverter forward direction phase rotation U, V, W. Connection as shown should produce clockwise direction when viewing the motor from the shaft end. Always test motor direction in both drive and bypass modes before coupling the motor to the load. 2. In the two contactor configuration, the M3 contactor is installed and controlled by an internal rocker switch. 3.
Document No. DPD01375 Installation Instructions August 24, 2018 NOTES: 1. 2. 3. Incoming power phase rotation should be L1, L2, L3 to match inverter forward direction phase rotation U, V, W. Connection as shown should produce clockwise direction when viewing the motor from the shaft end. Always test motor direction in both drive and bypass modes before coupling the motor to the load. 100kAIC SCCR achieved only when customer branch circuit protection is installed using the specified fuses from Table 8.
Document No. DPD01375 Installation Instructions August 24, 2018 NOTES: 1. Incoming power phase rotation should be L1, L2, L3 to match inverter forward direction phase rotation U, V, W. Connection as shown should produce clockwise direction when viewing the motor from the shaft end. Always test motor direction in both drive and bypass modes before coupling the motor to the load. 2. In the two contactor configuration, the M3 contactor is installed and controlled by an internal rocker switch. Figure 42.
Document No. DPD01375 Installation Instructions August 24, 2018 Wiring Diagrams Motor Rotation Correction Wiring Figure 44. Rotation Correction – VFD Correct, Bypass Reversed. Figure 45. Rotation Correction – VFD Reversed, Bypass Correct. Figure 46. Rotation Correction – VFD Reversed, Bypass Reversed. Page 32 of 36 Siemens Industry, Inc.
Document No. DPD01375 Installation Instructions August 24, 2018 Table 8. Customer-Supplied Branch Circuit Protection Fuse Chart. HP kW 1 1.5 2 3 5 7.5 10 15 20 25 30 40 50 60 75 100 125 150 200 0.75 1.1 1.5 2.2 4 5.5 7.5 11 15 18.5 22 30 37 45 55 75 90 110 132 250 160 Frame Size 4 4 5 6 5 7 6 8 7 9 8 208-240 Vac 460-500 Vac Current (A) Fuse 4.8 6.7 8.0 11.0 18.0 24.2 31.0 48.0 62.0 75.0 88.0 105.0 143.0 170.0 208.0 261.0 310.
Document No. DPD01375 Installation Instructions August 24, 2018 Table 10. Siemens Bypass Class 10 Overload Relay Setting Data – 460 Volt. Overload Page 34 of 36 HP kW 1.5 2 3 5 7.5 10 15 20 25 30 40 50 60 75 100 125 150 200 250 1.1 1.5 2.2 4 5.5 7.5 11 15 18.5 22 30 37 45 55 75 90 110 132 160 Frame Size 4 5 6 7 8 9 Drive FLA NEC FLA 3.4 4.8 5.6 9.6 12.0 16.0 23.0 31.0 38.0 46.0 61.0 72.0 87.0 105.0 140.0 170.0 205.0 261.0 310.0 3.0 3.4 4.8 7.6 11.
Document No. DPD01375 Installation Instructions August 24, 2018 Figure 47. Standard Motor Overload. NOTE: Set the overload relay by rotating the adjustment knob so that the arrow is aligned with the desired overload threshold, calibrated in Amps. The Siemens overloads provided with the bypass units are set at the factory according to the NEC motor tables. For proper protection, adjust the overload to the FLA of the connected motor. The provided overloads are designed for 125% load.
Document No. DPD01375 Installation Instructions August 24, 2018 Figure 49. Customer Power Input Line Connections, Typical Circuit Breaker Models. Figure 50. Customer Power Motor Connections, Typical for All Models. Issued by Siemens Industry, Inc. Building Technologies Division 1000 Deerfield Pkwy Buffalo Grove IL 60089 +1 847-215-1000 Document ID: DPD01375 Edition: 2018-08-24 © Siemens Industry, Inc., 2018 Technical specifications and availability subject to change without notice.