User Manual
111
4.4.3. Reflection of the profile on BACS efficiency factors
Operation and user profile impact BACS efficiency factors differently. Their impacts on BACS
efficiency is shown in the following table: Thermal for non-residential buildings:
Non-residential building types
BACS efficiency factors thermal f
BAC,th
D C B A
Non energy
efficient
Standard
(reference)
Advanced
energy
efficiency
High energy
performance
Offices
1.51 1 0.80 0.70
Lecture halls
1.24 1 0.75 0.5
a
Educational buildings (schools)
1.20 1 0.88 0.80
Hospitals
1.31 1 0.91 0.86
Hotels
1.31 1 0.85 0.68
Restaurants
1.23 1 0.77 0.68
Wholesale and retail buildings
1.56 1 0.73 0.6
a
a
The values are highly dependent on heating/cooling demand for ventilation
Operation profile
User profile