Remarks of Siemens
This section outlines how Siemens interprets the functions and processing functions according
to EN 15232-1:2017.
1) Plants required for "emission control" of thermal energy (e.g. radiators, chilled ceilings, VAV
systems) may have different supply media (e.g. water, air, electricity). As a result, different BAC
solutions may be possible for a processing function.
2) The Siemens interpretation gives full consideration to the processing function in the function list of
EN 15232:
· It includes thermostatic valves and electronic control equipment.
· Non-communicating electronic control equipment may include a local scheduler, but
experience suggests that they are often not correctly set
· For „Cooling Control“ thermostatic valves are not utilized
3) Communication between a superposed centralized unit and electronic individual room controllers
allow for centralized schedulers, monitoring of individual room controllers as well as centralized
operation and monitoring.
4) Demand control (by use) = demand control based on occupancy information from a presence
detector or a presence button with automatic reset after a set period. Control switches from
PreComfort to Comfort or vice versa using this occupancy information (see EN 15500).
Notes:
· Air quality control is considered by "Ventilation and air conditioning control"
· Occupancy information can influence "heating control", "cooling control" and "ventilation and
air conditioning control"
Note:
Setpoints for heating and cooling should be configured so that the setpoint range is as wide as
possible (with summer and winter compensation) to meet present use and comfort requirements.