Remarks of Siemens
This section outlines how Siemens interprets the functions and processing functions according
to EN 15232-1:2017.
5) The following main features distinguish TABS from other heating and cooling systems:
· TABS is a low-temperature heating/high temperature cooling system
· TABS activates relatively large thermal storage
These features permit energy-efficient operation in a number of cases
6) As a rule, there is only a single flow temperature setpoint per zone (heating and cooling – no
setpoint range. This means: Frequently slight overheating or undercooling during transition
periods (where heating and cooling are released).
7) A setpoint range is used here; one setpoint each can be preset separately for heating and
cooling. This eliminates to some extent overheating or undercooling.