This section outlines how Siemens interprets the functions and processing functions according
to EN 15232-1:2017.
1) The Plants required for "emission control" of thermal energy, such as fan coils, chilled ceilings or
VAV systems may have different supply media (e.g. water, air). As a result, different BAC
solutions may be possible for a processing function.
2) The Siemens interpretation gives full consideration to the processing function in the function list of
EN 15232:
· It includes thermostatic valves and electronic control equipment.
· Non-communicating electronic control equipment may include a local scheduler.
But experience suggests that they are often not correctly set.
· Thermostatic valves are not used for "cooling control".
3) Communication between a superposed centralized unit and electronic individual room controllers
allows for centralized schedulers, monitoring of individual room controllers as well as centralized
operation and monitoring.
4) Demand control (by use) = demand control based on occupancy information from a presence
detector or a presence button with automatic reset after a set period. Control switches from Pre-
Comfort to Comfort or the other way around using this occupancy information (see EN 15500).
Note:
· Air quality control is considered in "Ventilation and air conditioning control".
· Occupancy information can influence "heating control", "cooling control" and "ventilation and
air conditioning control".