Remarks of Siemens
This section outlines how Siemens interprets the functions and processing functions according
to EN 15232-1:2017.
1) A warning function overrides the turn-off signal by the user when using a scheduler to turn off
lighting.
For switchable lights, they are flashed on/off and turned off after a grace period unless overridden
by a user.
For dimmable lights, they are dimmed to a preset warning level and turned off after a grace period
unless overridden by a user.
2) They provide the highest energy savings as lights are typically manually turned on by the user at
lower light levels than is required for occupancy detectors that automatically turn lights on.