7.2 VAV control of CO2 and VOC
(A) Desigo Room Automation
with room sensors
Room controller DXR2..
Sensors
AQR2540NF + AQR2532NNW
Analog T output
and
AQR2548NF + AQR2530NNW
Analog IAQ output
(higher value of VOC and CO2)
Note: CO2 only analog output is
also possible
GDB181.1E/KN, or
GLB181.1E/KN
Connected to DXR2..
by KNX PL-Link
or
GDB181.1E/3, or
GLB181.1E/3
Connected to DXR2..
by DC 0/2…10 V (not shown)
VAV control of combined CO
2 and VOC
Supply and extract air control
External flow control for VAV with flow controller
and diff. pressure sensor
Internal flow controller and diff. pressure sensor, or air speed sensor
Cooling coil, heating/cooling coil, heating coil
Electric heating coil, modulating, single- or 2-stage
Room temperature control by 2-pipe system with c/o or 4-pipe system
Supply air temperature cascade control,
air flow tracking for under/overpressure
Radiator and chilled/heated ceiling control
IAQ control
VAV system with cooling
VAV system with heating/cooling
VAV system with electric heating coil
Note: similar applications available for fan powered box