Page 20 Unrestricted 0 – Siemens Smart infrastructure
The following products DXR1.. and DXR2.. combine a Desigo room controller and a VAV
compact controller in one hardware device. The DXR1.. is for HVAC only applications.
The DXR2.. also covers room electrical applications such as lighting and shading control.
BACnet IP
VAV actuating room
controller
DXR1.E09PDZ..
DXR1.E04PDZ..
DXR1.E10PL..
DXR2.E10PL..
Features
Communication (field bus) None KNX PL-Link
KNX LTE
KNX PL-Link
KNX LTE-/S-Mode
Torque (Nm) 5 10 10
Air damper area (m
2
) 0.8 1.5 1.5
Operating range (Pa) 0…500 0…500 0…500
Operating voltage (AC) 24 24 24
BACnet MS/TP
VAV actuating room
controller
DXR1.M09PDZ..
DXR1.M04PDZ..
DXR2.M10PL..
Features
Communication
(field bus)
None KNX PL-Link
KNX LTE-/S-Mode
Torque (Nm) 5 10
Air damper area (m
2
) 0.8 1.5
Operating range (Pa) 0…500 0…500
Operating voltage (AC) 24 24